190
SAW sensor – Parameter
Type 8098 FLOWave L
15.8.4 Deactivating the damping of the liquid velocity values
By default, the liquid velocity values are not damped.
But if the damping of the liquid velocity values is active, do the following to deactivate it:
Go to the CONFIGURATION view.
SAWsensor
Parameter view.
Stand.meas.values
Liquidvelocity
Damping The Currentsettings are displayed
None The Newsettings are displayed.

The damping of the liquid velocity values is inactive.
15.8.5 Activating the monitoring of the liquid velocity

too high or too low.
A monitored value can be:
in the normal operating range.
in the warning range,
in the error range.
You can set 4 limit values: 2 error limits and 2 warning limits.

of the liquid velocity.
 in 

and if the monitored value increases or decreases.
By default, the monitoring of the liquid velocity and the diagnostics are all disabled.
To activate the monitoring of the liquid velocity, do the following:
Go to the CONFIGURATION view.
SAWsensor
Parameter view.
Stand.meas.values
Liquidvelocity