211
SAW sensor – Parameter
Type 8098 FLOWave L
15.11.4 Deactivating the monitoring of each mass totalizer
By default, the mass totalizers are not monitored.
But if the monitoring of a mass totalizer is active, do the following to deactivate it:
Go to the CONFIGURATION view.
SAWsensor
Parameter view.
Stand.meas.values
Masstotalizer1 or Masstotalizer2
Limits
Active
No.

The monitoring of the mass totalizer is inactive.
15.11.5 Changing the error limits, the warning limits and the hysteresis
of each mass totalizer
To change the error limits, the warning limits and the hysteresis of each mass totalizer, do the following:
Go to the CONFIGURATION view.
SAWsensor
Parameter view.
Stand.meas.values
Masstotalizer1 or Masstotalizer2
Limits
Settings The Currentsettings are displayed




 The Newsettings are displayed.

The limit values and the hysteresis value are changed.