WindO/I-NV4 User’s Manual 15-17
3 Operation Log Settings Dialog Box
15
Operation Log Function
Real Time
Select this check box to output data to the external memory device
*1
in real time.
With real time output, data is saved to the external memory device
*1
in three minute intervals after the MICRO/I starts
running. If the accumulated data reaches 80% of the amount set in the Data Storage Area, then the data is forcibly
saved to the external memory device
*1
. When there is already data with the same file name on the external memory
device
*1
, data is appended to that file. If there was no update to the data during the three minutes, it is not output.
Data is appended to the file until the size of the file reaches the restriction size (256 MB), so the maximum amount of
output data varies based on the settings for the output channel such as the amount of data, the data size, and the labels.
If the interval events occur more quickly than the time it takes to accomplish the real time output (the interval for writing
to the external memory device
*1
), the Operation Log is recorded up to the data storage amount - 1, and then
afterwards, old data is discarded in order and replaced with new data.
*1 USB flash drive inserted in USB1 for HG2J-7U, SD memory card for HG5G/4G/3G/2G-V, HG4G/3G and HG2G-5F,
USB flash drive for HG2G-5T and HG1G/1P
MICRO/I
Operation Log data
(CSV)
Output to
External memory device
Operation Log data
Sampling Time User Screen No. Event Name Part Name Details Changed to
12/01/2011 12:00:10 - Base1 Power ON - - -
12/01/2011 12:01:23 User1 Base1 Switch to Base Screen - - Base2
12/01/2011 12:02:45 User1 Base2 Change Users - - User2
12/01/2011 12:03:06 User2 Base2 Change Operation Modes - - System Mode
12/01/2011 12:04:11 User2 Base2 Press buttons BitSwitch - -
12/01/2011 12:04:11 User2 Base2 Write Data to any Device Addresses - LDR0 55
12/01/2011 12:07:30 User2 Base2 Switch to Base Screen - - Base3
3 minute interval
after operation starts
Data to be output
3 minutes after
operation starts
Data to be output
3 minutes
after that
Data to be output
after another
3 minutes
External memory device
USB flash drive
SD memory card
Real time output stops when the file size of the Operation Log data exceeds 256 MB or when there is
insufficient space on the external memory device. The error information is stored in the following HMI
Special Data Registers. For details about the error information, refer to Chapter 33 “HMI Special Data
Register (LSD)” on page 33-8.
HG2J-7U, HG5G/4G/3G/2G-V, HG4G/3G, HG2G-5F: LSD42
HG2G-5T, HG1G/1P: LSD33
When the value of the following HMI Special Internal Relays changes from 0 to 1, the data at that time is
first output in real time to the external memory device, and then access to the external memory device is
stopped. For details, refer to Chapter 33 “HMI Special Relay (LSM)” on page 33-2.
HG2J-7U, HG5G/4G/3G/2G-V, HG4G/3G, HG2G-5F: LSD20
HG2G-5T, HG1G/1P: LSD18
The amount of free space on the external memory device is saved to the following HMI Special Data
Registers. For details about the free space on the External Memory Devices, refer to Chapter 33 “HMI
Special Data Register (LSD)” on page 33-8.
HG2J-7U, HG5G/4G/3G/2G-V, HG4G/3G, HG2G-5F: LSD43, 44
HG2G-5T, HG1G/1P: LSD34, 35

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC WindO/I-NV4 and is the answer not in the manual?

IDEC WindO/I-NV4 Specifications

General IconGeneral
BrandIDEC
ModelWindO/I-NV4
CategoryOrganizer
LanguageEnglish