iView - Controller View
9-36 Manual # 42-02-7223
• Car riding: Enable if car-riding arrival notification devices are used for this car.
• Deactivate car lanterns when door dwell time has elapsed: Set this option to deactivate
the car lanterns/gongs as soon as the door dwell time has expired and the doors start
to close. Otherwise the car lanterns will remain ON until the doors have fully closed.
• Double strike for down direction: Sound car-riding arrival fixtures twice when
announcing down direction arrival. If the fixtures themselves support double-striking,
this feature should not be enabled.
• Set the On timer for the amount of time the gong output should be active. Set the Off
timer to establish the pause between first and second gongs.
• Passing floor gong: Set the On timer for the amount of time the gong output should be
active. Set the Off timer to establish the minimum pause between gongs.
Emergency Alarm Monitoring:
• Enable: Enables emergency alarm monitoring.
• Monitor alarm button input: By default, the alarm button alarm input is monitored
with visible and audible indicators driven by the Alarm Light and Alarm Buzzer out-
puts.
• Monitor in-car stop switch: By default, the in-car stop switch is monitored with visible
and audible indicators driven by the Alarm Light and Alarm Buzzer outputs.
• Monitor car delayed with doors closed: When enabled, if the car is delayed with doors
closed an amount of time in excess of the Car delayed timer setting, the Alarm Light
and Alarm Buzzer outputs will be activated.
• Monitor safety circuit open: If enabled, any condition that causes a safety string
switch, contact, or relay to open will activate the Alarm Light and Alarm Buzzer out-
puts.
• Require acknowledgement: Requires that the emergency alarm be acknowledged in
order to turn off the Alarm light and buzzer. Typically this is done via the Alarm Reset
input.
• Allow software acknowledgement: If enabled, emergency alarms may also be
acknowledged via iMonitor.
Note:
Alarm Light: Typically, the Alarm Light is placed where it will be visible to security person-
nel. The output remains latched until acknowledged by activation or the Alarm Reset input
(typically a keyed switch).
Alarm Buzzer: Typically, the Alarm Buzzer is placed where it will be audible to security per-
sonnel. The standard (in-car stop or alarm open) output is constant and causes a constant
tone. The additional (delayed with doors closed or other open safety condition) output is
pulsating and causes a pulsating tone. This output does not latch but remains active only so