iView - Controller View
9-56 Manual # 42-02-7223
Fire Code - In-Car - General Tab
This tab allows you to set In-Car Firefighter parameters.
• Fire Phase II Recall Conditions: One of the following conditions is required to initiate Fire
Phase II recall when the Fire Phase II switch is deactivated.
• No recall: Never recall.
• Recall: Always initiate recall.
• Doors open or closed: Initiate recall only if the doors are fully open or closed.
• Phase 1 and doors open: Initiate recall only if Phase I is still active and the doors are
fully open.
• Phase I and doors open or closed: Initiate recall only if Phase I is still active and the
doors are fully open or closed.
• Primary ON and doors opened once: Initiate recall only if the Primary Fire Recall
switch is in the On position and the doors have been opened at least once at the floor.
• Doors open: Initiate recall only if the doors are fully open.