EasyManua.ls Logo

MCE iControl - Fire Service - Fire Code

Default Icon
806 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration - Car Operation
9-49
9
iControl DC
Fire Service - Fire Code
Displays the currently selected Fire Code and allows a different Fire Code to be selected.
All parameters are in default state: Indicates that all of the fire service parameters
are set as specified by the selected code. If this is not the case, “One or more parameters
has been changed.” is displayed.
Name: Select the appropriate code from the drop down list.
Year: Select the appropriate version (year) of the code.
Default button: Sets the fire service parameters to the values specified by the selected
code, e.g. A17.1 - 2000.
Latch the fire hat flashing: Flashing the fire hat is required by certain jurisdictions
whenever the hoistway or machine room smoke sensors are tripped. When these sensors
are reset, the fire hat continues to flash if this option is set. Otherwise the fire hat will
remain illuminated until fire service is deactivated.
Flash fire hat if recall is initiated by the machine room or hoistway sensors:
The fire hat will flash if the recall is initiated by the machine room or hoistway sensors.