iView - Controller View
9-52 Manual # 42-02-7223
Latch secondary fire recall switch:
Never: The recall condition will clear automatically when the initiating condition
clears.
Fire device OFF: In order to clear the recall condition, the secondary fire recall switch
must be off.
Primary bypass: In order to clear the recall condition, the primary fire recall switch
must be turned to the BYPASS position.
Bypass and recall completed: In order to clear the recall condition, the car must be at
the fire floor with doors open and the primary fire recall switch must be turned to the
BYPASS position.
Recall completed all cars: In order to clear the recall condition, the fire recall must be
completed for all elevators in the group.
Primary bypass then OFF: In order to clear the recall condition, the primary fire recall
switch must be turned to the BYPASS position and then back to off.
Latch first smoke detector zone:
Never: The recall condition will clear automatically when the initiating condition
clears. When this option is set, the main floor smoke sensor will override the upper
floor smoke sensors.
Fire device OFF: In order to clear the recall condition, the secondary fire recall switch
must be off.
Primary bypass: In order to clear the recall condition, the primary fire recall switch
must be turned to the BYPASS position.
Bypass and recall completed: In order to clear the recall condition, the car must be at
the fire floor with doors open and the primary fire recall switch must be turned to the
BYPASS position.
Recall completed all cars: In order to clear the recall condition, the fire recall must be
completed for all elevators in the group.
Primary bypass then OFF: In order to clear the recall condition, the primary fire recall
switch must be turned to the BYPASS position and then back to off.
Fire Phase 1 nudging:
No nudging: During Fire Phase I, nudging will be inhibited.
Nudge if no reopen devices: During Fire Phase I, the doors will nudge close if there are
no operative reopening devices.
Disable DOB and nudge during Fire Phase I:
Not at all: The Door Open button will remain active.
Immediately: The Door Open button will immediately become inactive when Fire
Phase I is initiated and the doors will nudge close if the Door Open Button is pressed as
the doors are closing.
After delay: The Door Open Button will become inactive after the set delay when Fire
Phase I has been initiated and the doors will nudge close if the Door Open Button is
pressed as the doors are closing.