Configuration - Car Operation
9-33
9
iControl DC
Door Close Fault Recovery:
Fault recovery attempts: (see Fault recovery timer).
Fault recovery timer: Timer starts when a Door Close Fault is detected. When the timer
expires, the Door Close Fault is cleared to allow the doors to again attempt to close. If
the doors still do not successfully close, another Door Close Fault is declared and the
Fault recovery timer runs again. When the number of recovery attempts reaches the
value of the Fault recovery attempts parameter, a Fault Recovery Failure is declared
and the message is displayed. The car is shut down until a mode change is detected or
the doors are successfully closed via constant pressure on the Door Close Button.
•Retiring cam:
Enable: Enables the retiring cam feature and motor protection functions.
Door lock attempts: The number of attempts made to lock the doors with the retiring
cam before declaring a Retiring Cam Door Lock fault and re-opening the doors.
Door lock protection timer: The amount of time to attempt to lock the doors with the
retiring cam before declaring a Retiring Cam Door Lock fault and re-opening the
doors.
Motor timer: The amount of time to energize the retiring cam motor in an attempt to
lock the doors before declaring a Retiring Cam Protection fault and re-opening the
doors.