2 Parameters
2.2 List of parameters
SINAMICS DCP
104 List Manual (LH21), 05/2016
Description: Sets the message type for the selected fault or alarm.
Value: 1: Fault (F)
2: Alarm (A)
3: No message (N)
Dependency: Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2118
Note: Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
The message type can only be changed for messages with the appropriate identification (exception, value = 0).
Example:
F12345(A) --> Fault F12345 can be changed to alarm A12345.
In this case, the message number that may be possibly entered in p2100[0...19] and p2126[0...19] is automatically
removed.
Description: Sets the message type for the selected fault or alarm.
Value: 1: Fault (F)
2: Alarm (A)
3: No message (N)
Dependency: Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2118
Note: Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
The message type can only be changed for messages with the appropriate identification (exception, value = 0).
Example:
F12345(A) --> Fault F12345 can be changed to alarm A12345.
In this case, the message number that may be possibly entered in p2100[0...19] and p2126[0...19] is automatically
removed.
Description: Displays the sum of all of the fault and alarm buffer changes in the drive unit.
Dependency: Refer to: r0944, r2121
Description: This counter is incremented every time the alarm buffer changes.
Dependency: Refer to: r2110, r2122, r2123, r2124, r2125
p2119[0...19] Change message type type / Change type type
CU_DCP, DCP_CTRL Can be changed: U, T Access level: 3
Data type: Integer16 Func. diagram: 8075
Min Max Factory setting
1 3 1
p2119[0...19] Change message type type / Change type type
TM150, TM15DI_DO,
TM31
Can be changed: U, T Access level: 3
Data type: Integer16 Func. diagram: 8050, 8075
Min Max Factory setting
1 3 1
r2120 CO: Sum of fault and alarm buffer changes / Sum buffer changed
All objects Can be changed: - Access level: 4
Data type: Unsigned16 Func. diagram: 8065
Min Max Factory setting
- - -
r2121 CO: Counter alarm buffer changes / Alrm buff changed
All objects Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 8065
Min Max Factory setting
- - -