2 Parameters
2.2 List of parameters
SINAMICS DCP
284 List Manual (LH21), 05/2016
Description: Display and BICO output for the status of the current setpoint.
Description: Sets the load profile.
If value = 0:
Short time current = base load current = rated device current
If value = 1:
Short time current = base load current = p55081 * rated device current
In this operating mode, at low ambient temperatures, an increased current is continuously permitted. However, the
temperature-dependent derating already starts at a lower ambient temperature than for operation without increased
current.
If value = 2:
Short time current = 150 % * base load current
If value = 3:
Short time current = 160 % * base load current
Value: 0: No overload
1: Increased current
2: Low overload
3: High overload
Description: Sets the permissible current increase for the load profile "increased current" (p55080 = 1).
Description: Display and connector output for various calculated temperatures.
Index: [0] = Barrier layer temperature at IGBT T1A
[1] = Barrier layer temperature at IGBT T1B
[2] = Barrier layer temperature at IGBT T2A
[3] = Barrier layer temperature at IGBT T2B
[4] = Barrier layer temperature at free-wheeling diode D1A
[5] = Barrier layer temperature at free-wheeling diode D1B
[6] = Barrier layer temperature at free-wheeling diode D2A
[7] = Barrier layer temperature at free-wheeling diode D2B
[8] = Maximum permissible barrier layer temperature
r55075.0...2 CO/BO: Current setpoint status / I_set status
DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 6805
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Setpoint very low Yes No 6805
01 Setpoint positive Yes No 6805
02 Setpoint negative Yes No 6805
p55080 Dynamic overload load profile / Dyn overload prof
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Integer16 Func. diagram: 6808
Min Max Factory setting
0 3 0
p55081 Dynamic overload current increase / Dyn overld I_incr
DCP_CTRL Can be changed: U, T Access level: 3
Data type: FloatingPoint32 Func. diagram: 6808
Min Max Factory setting
0.00 [%] 20.00 [%] 0.00 [%]
r55082[0...8] CO: Dynamic overload temperatures calculated / Dyn overld T_calc
DCP_CTRL Can be changed: - Access level: 3
Data type: FloatingPoint32 Func. diagram: 6808
Min Max Factory setting
- [°C] - [°C] - [°C]