2 Parameters
2.2 List of parameters
The address can be set as follows:
Via p0918
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
Note: Permissible PROFIBUS addresses: 1 ... 126
Address 126 is used for commissioning.
Every PROFIBUS address change only becomes effective after a POWER ON.
Description: Sets the send and receive telegram.
Value: 999: Free telegram configuration with BICO
Description: Sets the send and receive telegram.
Value: 999: Free telegram configuration with BICO
Dependency: Refer to: F01505, F01506
Note: For p0922 = 100 ... 199, p2038 is automatically set to 1 and p2038 can no longer be changed. This means that for
these telegrams, the "SIMODRIVE 611 universal" interface mode is set and cannot be changed.
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are
inhibited.
The inhibited interconnections can only be changed again after setting value 999.
Description: Displays the position of the "Pulses enabled" status signal in the PROFIdrive telegram.
Index: [0] = Signal number
[1] = Bit position
Description: Displays fault buffer changes. This counter is incremented every time the fault buffer changes.
Recommendation: Used to check whether the fault buffer has been read out consistently.
Dependency: Refer to: r0945, r0947, r0948, r0949, r2109
Description: Displays the numbers of faults that have occurred.
p0922 IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr
CU_DCP Can be changed: C2(1), T Access level: 1
Data type: Unsigned16 Func. diagram: 1520, 2420
Min Max Factory setting
999 999 999
p0922 IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr
DCP_CTRL Can be changed: C2(1), T Access level: 1
Data type: Unsigned16 Func. diagram: 1520, 2420
Min Max Factory setting
999 999 999
r0924[0...1] ZSW bit pulses enabled / ZSW pulse enab
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
r0944 CO: Counter for fault buffer changes / Fault buff change
All objects Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 8060
Min Max Factory setting
- - -
r0945[0...63] Fault code / Fault code
CU_DCP, DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 8060
Min Max Factory setting
- - -