2 Parameters
2.2 List of parameters
SINAMICS DCP
28 List Manual (LH21), 05/2016
Description: Sets the parameter filter for commissioning a Terminal Module 150 (TM150).
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
For the BOP, this setting also causes the read access operations to be filtered.
Value: 0: Ready
29: Only Siemens int
30: Parameter reset
Dependency: Refer to: p0970
Note: Only the following values are possible: p0010 = 0, 30
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Description: Sets the parameter filter for commissioning a Terminal Module 15 (TM15).
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
For the BOP, this setting also causes the read access operations to be filtered.
Value: 0: Ready
29: Only Siemens int
30: Parameter reset
Dependency: Refer to: p0970
Note: Only the following values are possible: p0010 = 0, 30
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Description: Sets the parameter filter for commissioning a Terminal Module 31 (TM31).
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
For the BOP, this setting also causes the read access operations to be filtered.
Value: 0: Ready
29: Only Siemens int
30: Parameter reset
Dependency: Refer to: p0970
Note: Only the following values are possible: p0010 = 0, 30
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Description: Sets the password for the Basic Operator Panel (BOP).
Dependency: Refer to: p0012, p0013
p0010 TM150 commissioning parameter filter / TM150 com par_filt
TM150 Can be changed: C2(1), T Access level: 1
Data type: Integer16 Func. diagram: -
Min Max Factory setting
0 30 0
p0010 TM15DI/DO commissioning the parameterizing filter / TM15D com par_filt
TM15DI_DO Can be changed: C2(1), T Access level: 1
Data type: Integer16 Func. diagram: -
Min Max Factory setting
0 30 0
p0010 TM31 commissioning parameter filter / TM31 comm par_filt
TM31 Can be changed: C2(1), T Access level: 1
Data type: Integer16 Func. diagram: -
Min Max Factory setting
0 30 0
p0011 BOP password entry (p0013) / BOP passw ent p13
CU_DCP Can be changed: U, T Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
0 65535 0