2 Parameters
2.2 List of parameters
SINAMICS DCP
110 List Manual (LH21), 05/2016
Description: Display and BICO output for the second status word of faults and alarms.
Description: Displays the system runtime in days when the fault was removed.
Dependency: Refer to: r0945, r0947, r0948, r0949, r2109, r2114, r2130, r2133, r3115, r3120, r3122
Notice: The time comprises r2136 (days) and r2109 (milliseconds).
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Description: Display and BICO output for the control word of faults and alarms.
Dependency: Refer to: p2103, p2104, p2105, p2106, p2107, p2108, p2112, p2116, p2117, p3110, p3111, p3112
Description: Display and BICO output for the control word of faults and alarms.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fault encoder 1 Yes No -
01 Fault encoder 2 Yes No -
02 Fault encoder 3 Yes No -
r2135.0...15 CO/BO: Status word faults/alarms 2 / ZSW fault/alarm 2
DCP_CTRL, TM150,
TM15DI_DO, TM31
Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 2548
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fault encoder 1 Yes No -
01 Fault encoder 2 Yes No -
02 Fault encoder 3 Yes No -
12 Fault motor overtemperature Yes No 8016
13 Fault power unit thermal overload Yes No 8014
14 Alarm motor overtemperature Yes No 8016
15 Alarm power unit thermal overload Yes No 8014
r2136[0...63] Fault time removed in days / t_flt resolv days
All objects Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 8060
Min Max Factory setting
- - -
r2138.7...15 CO/BO: Control word faults/alarms / STW fault/alarm
CU_DCP, DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 2546, 8060,
8065
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
07 Acknowledge fault Yes No 8060
10 External alarm 1 (A07850) effective Yes No 8065
11 External alarm 2 (A07851) effective Yes No 8065
12 External alarm 3 (A07852) effective Yes No 8065
13 External fault 1 (F07860) effective Yes No 8060
14 External fault 2 (F07861) effective Yes No 8060
15 External fault 3 (F07862) effective Yes No 8060
r2138.7...15 CO/BO: Control word faults/alarms / STW fault/alarm
TM150, TM15DI_DO,
TM31
Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 2546
Min Max Factory setting
- - -