SINAMICS DCP
List Manual (LH21), 05/2016
279
2 Parameters
2.2 List of parameters
Description: Sets the signal source for the "enable" signal of the battery charging characteristic.
Description: Sets the voltage values for the battery charging characteristic.
Every point comprises a voltage/current value pair: p54210[x]/p54211[x]
Points along the characteristic:
r54210[0]: voltage value characteristic point 0
r54211[0]: current value characteristic point 0
r54210[1]: voltage value characteristic point 1
r54211[1]: current value characteristic point 1
r54210[2]: voltage value characteristic point 2
r54211[2]: current value characteristic point 2
r54210[3]: voltage value characteristic point 3
r54211[3]: current value characteristic point 3
Dependency: Refer to: p54211
Note: Linear interpolation is realized between the individual points.
The voltages of the characteristic points must be set to increase monotonously and they must differ by at least 1 V.
Description: Sets the current values for the battery charging characteristic.
Every point comprises a voltage/current value pair: p54210[x]/p54211[x]
Points along the characteristic:
r54210[0]: voltage value characteristic point 0
r54211[0]: current value characteristic point 0
r54210[1]: voltage value characteristic point 1
r54211[1]: current value characteristic point 1
r54210[2]: voltage value characteristic point 2
r54211[2]: current value characteristic point 2
r54210[3]: voltage value characteristic point 3
r54211[3]: current value characteristic point 3
Note: Linear interpolation is realized between the individual points.
p54204 BI: Battery charging characteristic enable signal source / Batt enab s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / Binary Func. diagram: 6720
Min Max Factory setting
- - 899.11
p54210[0...3] Battery charging characteristic voltage values / Batt U_values
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6720
Min Max Factory setting
0.00 [V] 2000.00 [V] [0] 600.00 [V]
[1] 650.00 [V]
[2] 680.00 [V]
[3] 690.00 [V]
p54211[0...3] Battery charging characteristic current values / Batt I_values
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6720
Min Max Factory setting
0.00 [A] 2000.00 [A] 50.00 [A]