SINAMICS DCP
List Manual (LH21), 05/2016
219
2 Parameters
2.2 List of parameters
Description: Displays the active standard gateway for the Communication Board Ethernet 20/25 (CBE20/CBE25).
Description: Displays the active subnet mask for the Communication Board Ethernet 20/25 (CBE20/CBE25).
Description: Displays the active DHCP mode for the Communication Board Ethernet 20/25 (CBE20/CBE25).
Notice: When the DHCP mode is active (parameter value greater than 0), PROFINET communication via this interface is no
longer possible! However, the interface can be used by the STARTER/SCOUT commissioning tool.
Note: If value = 0:
DHCP deactivated.
If value = 2:
DHCP activated. The MAC address of this interface is used for client identification.
If value = 3:
DHCP activated. The station name of this interface is used for client identification.
Description: Displays the MAC address for the Communication Board Ethernet 20/25 (CBE20/CBE25).
Description: Displays the DAP ID for PROFINET via the Communication Board Ethernet 20/25 (CBE20/CBE25).
The combination of device ID (r8909) and DAP ID (r8959) uniquely identifies a PROFINET access point.
Note: DAP ID: Device Access Point ID
DAP ID = 20007 hex: SINAMICS CBE20 V4.5
DAP ID = 20008 hex: SINAMICS CBE20 V4.6
DAP ID = 20009 hex: SINAMICS CBE20 V4.7
DAP ID = 20209 hex: SINAMICS CBE25 V4.7
r8952[0...3] CBE2x Default Gateway of Station active / CBE2x def GW act
CU_DCP (PROFINET
CBE20)
Can be changed: - Access level: 3
Data type: Unsigned8 Func. diagram: -
Min Max Factory setting
0 255 -
r8953[0...3] CBE2x Subnet Mask of Station active / CBE2x Sub Mask act
CU_DCP (PROFINET
CBE20)
Can be changed: - Access level: 3
Data type: Unsigned8 Func. diagram: -
Min Max Factory setting
0 255 -
r8954 CBE2x DHCP Mode active / CBE2x DHCP act
CU_DCP (PROFINET
CBE20)
Can be changed: - Access level: 3
Data type: Unsigned8 Func. diagram: -
Min Max Factory setting
0 255 -
r8955[0...5] CBE2x MAC Address of Station / CBE2x MAC Addr
CU_DCP (PROFINET
CBE20)
Can be changed: - Access level: 3
Data type: Unsigned8 Func. diagram: -
Min Max Factory setting
0000 hex 00FF hex -
r8959 CBE2x DAP ID / CBE2x DAP ID
CU_DCP (PROFINET
CBE20)
Can be changed: - Access level: 3
Data type: Unsigned32 Func. diagram: -
Min Max Factory setting
0000 hex FFFF FFFF hex -