2 Parameters
2.2 List of parameters
SINAMICS DCP
204 List Manual (LH21), 05/2016
Description: Assignment of a PZD to a telegram word from a SINAMICS Link receive telegram.
For p8839[0] = 2 (COMM BOARD via interface 1), the following applies:
- PZD p2050[index] is assigned by means of p8870[index], p8872[index].
For p8839[1] = 2 (COMM BOARD via interface 2), the following applies:
- PZD p8850[index] is assigned by means of p8870[index], p8872[index].
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
Dependency: Refer to: p8872
Note: Value range:
0: Not used
1 ... 16: Telegram word
A pair of values p8870[index], p8872[index] may only be used once in single a device.
A change only becomes effective after POWER ON, reset, project download or p8842 = 1.
Description: Assigns a PZD to a telegram word in the SINAMICS Link send telegram.
For p8839[0] = 2 (COMM BOARD via interface 1), the following applies:
- p8871[index] assigns PZD p2051[index].
For p8839[1] = 2 (COMM BOARD via interface 2), the following applies:
- p8871[index] assigns PZD p8851[index].
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
p8870[0...15] SINAMICS Link receive telegram word PZD / Recv link word
DCP_CTRL
(PROFINET CBE20),
TM150 (PROFINET
CBE20), TM15DI_DO
(PROFINET CBE20),
TM31 (PROFINET
CBE20)
Can be changed: T Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
0 16 0
p8871[0...15] SINAMICS Link send telegram word PZD / Send link word
TM150 (PROFINET
CBE20), TM15DI_DO
(PROFINET CBE20),
TM31 (PROFINET
CBE20)
Can be changed: T Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
0 16 0