2 Parameters
2.2 List of parameters
SINAMICS DCP
22 List Manual (LH21), 05/2016
2.2 List of parameters
Product: SINAMICS DCP, Version: 4703500, Language: eng
Objects: CU_DCP, DCP_CTRL, TM150, TM15DI_DO, TM31
Product: SINAMICS DCDC_V, Version: 1200700, Language: eng
Objects: DCP_CTRL
Description: Operating display for the Control Unit (CU).
Value: 0: Operation
10: Ready
20: Wait for run-up
25: Wait for automatic FW update of DRIVE-CLiQ components
31: Commissioning software download active
33: Remove/acknowledge topology error
34: Exit commissioning mode
35: Carry out first commissioning
70: Initialization
80: Reset active
99: Internal software error
Notice: For several missing enable signals, the corresponding value with the highest number is displayed.
Description: Operating display for the drive.
Value: 0: o0.0 No torque direction switched on
1: o0.1 Torque direction I switched on
12: o1.2 Wait for operating enable (signal source acc. to p0852)
16: o1.6 Wait for withdrawal of the immediate pulse inhibit
31: o3.1 Wait for line supply symmetry
40: o4.0 Wait for voltage at 1U1, 1V1, 1W1
41: o4.1 Wait until fuse monitoring signals OK
71: o7.1 Wait for power-on (signal source according to p0840)
80: o8.0 Switching on inhibited
81: o8.1 Simulation mode active
91: o9.1 Quick stop (OFF3) (signal source acc. to p0848) present
92: o9.2 Quick stop (OFF3) (signal source acc. to p0849) present
101: o10.1 Voltage disconnect (OFF2) (signal source acc. to p0844)
102: o10.2 Voltage disconnect (OFF2) (signal source acc. to p0845)
103: o10.3 E stop (safety shutdown) (terminal 105/106)
110: o11.0 Fault present
121: o12.1 Initializ. of line voltage sensing for armature in progr.
123: o12.3 Reading out data of the gating modules
124: o12.4 Offset calibr. of curr. act. val. sensing being performed
125: o12.5 Read out data from the power unit
126: o12.6 Initializing the second processor (TMS320)
Notice: For several missing enable signals, the corresponding value with the highest number is displayed.
Note: OC: Operating condition
RFG: Ramp-function generator
COMM: Commissioning
r0002 Control Unit operating display / CU op_display
CU_DCP Can be changed: - Access level: 1
Data type: Integer16 Func. diagram: 2651
Min Max Factory setting
0 99 -
r0002 Drive operating display / Drv op_display
DCP_CTRL Can be changed: - Access level: 1
Data type: Integer16 Func. diagram: 2651
Min Max Factory setting
0 126 -