Siemens sinamics dcp - p4073[0...1] TM31 analog outputs smoothing time constant; TM31 AO T_smooth; r4074[0...1] TM31 analog outputs current output voltage;current; TM31 AO U;I_outp; p4075[0...1] TM31 analog outputs activate absolute value generation; TM31 AO absVal act; p4076[0...1] TM31 analog outputs type; TM31 AO type

Siemens sinamics dcp
518 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS DCP
140 List Manual (LH21), 05/2016
Description: Sets the smoothing time constant of the 1st-order low pass filter for the analog outputs of Terminal Module 31
(TM31).
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Description: Displays the actual output voltage in V when set as voltage output.
Displays the actual output voltage in mA when set as current output.
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency: The type of the analog output AO x (voltage or current output) is set using p4076.
Refer to: p4076
Note: AO: Analog Output
Description: Activates the absolute value generation for the analog outputs of Terminal Module 31 (TM31).
Value: 0: No absolute value generation
1: Absolute value generation switched in
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Description: Sets the type of analog outputs of Terminal Module 31 (TM31).
p4076[x] = 1, 4 correspond to a voltage output (p4074, p4078, p4080, p4083 are displayed in V).
p4076[x] = 0, 2, 3 correspond to a current output (p4074, p4078, p4080, p4083 are displayed in mA).
Value: 0: Current output (0 mA ... +20 mA)
1: Voltage output (0 V ... +10 V)
2: Current output (+4 mA ... +20 mA)
3: Current output (-20 mA ... +20 mA)
4: Voltage output (-10 V ... +10 V)
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency: Refer to: p4077, p4078, p4079, p4080
Note: When changing p4076, the parameters of the scaling characteristic (p4077, p4078, p4079, p4080) are overwritten
with the following default values:
For p4076 = 0, 3, p4077 is set to 0.0 %, p4078 to 0.0 mA, p4079 to 100.0 % and p4080 to 20.0 mA.
For p4076 = 1, 4, p4077 is set to 0.0 %, p4078 to 0.0 V, p4079 to 100.0 % and p4080 to 10.0 V.
For p4076 = 2, p4077 is set to 0.0 %, p4078 to 4.0 mA, p4079 to 100.0 % and p4080 to 20.0 mA.
p4073[0...1] TM31 analog outputs smoothing time constant / TM31 AO T_smooth
TM31 Can be changed: U, T Access level: 1
Data type: FloatingPoint32 Func. diagram: 9572
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 0.0 [ms]
r4074[0...1] TM31 analog outputs current output voltage/current / TM31 AO U/I_outp
TM31 Can be changed: - Access level: 1
Data type: FloatingPoint32 Func. diagram: 9572
Min Max Factory setting
- - -
p4075[0...1] TM31 analog outputs activate absolute value generation / TM31 AO absVal act
TM31 Can be changed: T Access level: 3
Data type: Integer16 Func. diagram: 9572
Min Max Factory setting
0 1 0
p4076[0...1] TM31 analog outputs type / TM31 AO type
TM31 Can be changed: U, T Access level: 1
Data type: Integer16 Func. diagram: 9572
Min Max Factory setting
0 4 4