EasyManua.ls Logo

Siemens sinamics dcp - Fig. 3-30 6808 - Dynamic overload

Siemens sinamics dcp
518 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Function diagrams
3.9 Closed-loop control
SINAMICS DCP
350 List Manual (LH21), 05/2016
Fig. 3-30 6808 – Dynamic overload
fp_6808_89.vsd
12345678
- 6808 -
SINAMICS DCP
25.04.2016 v 1.2
DO: DCP_CTRL
- Dynamic Overload
Function diagram
r55520
ActVal I_re SumAvg [%]
Dyn overload prof
p55080
A60039
Dyn overload T too high
r55083
Dyn overld I_lim [%]
&
+
+
r55071
I_set reactor [%]
1
0
Thermal model
of power unit
Priority:
1. RESET
2. SET
16,000 μs
[1020.7]
SET
(Q=1)
Q
RESET
(Q=0)
Q
B>A
A
B
±2°C
[6810.4]
[6850.2]
r55085.0
Thresh temp exc
+
r55085.1
CondA60039 fulfill
[6805.7]
0
1
+
+
Air intake temperature sensor
 > 45°
A60502
AirIntTmp too high
+
basic current
short-time current
porperties
of
power stack
maximum temperature
Dyn overld I_incr
p55081
p55101[0]
Reduce temp_thresh
r55082[8]
Barr lay_temp max
r55082[0]
Temp IGBT T1A
r55082[7]
Temp diode D2B
+
+
+
+
+
+
+
+
+
Maximum
r55084
Dyn overld P_loss [W]
r52050[5]
Air intake temp
r52051[0]
Temp PU1
r52051[1]
Temp PU2
r52051[2]
Temp PU3
Maximum
[8048.2]
[8048.2]
[8048.2]
load cycle
monitoring
r55091
Dyn overload t_sig [%]
DynOverld t_overld
p55090
r55520
ActVal I_re SumAvg [%]
[6850.2]
F60530
Dyn overload temp too high

Table of Contents

Other manuals for Siemens sinamics dcp

Related product manuals