EasyManua.ls Logo

Siemens sinamics dcp - p2098[0...1] Inverter connector-binector converter binector output; Con;bin outp inv; p2099[0...1] CI: Connector-binector converter signal source; Con;bin S_src

Siemens sinamics dcp
518 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS DCP
96 List Manual (LH21), 05/2016
Description: Setting to invert the individual binector outputs of the connector-binector converter.
Using p2098[0], the signals of connector input p2099[0] are influenced.
Using p2098[1], the signals of connector input p2099[1] are influenced.
Dependency: Refer to: r2094, r2095, p2099
Description: Sets the signal source for the connector-binector converter.
A PZD receive word can be selected as signal source. The signals are available to be serially passed-on
(interconnection).
Dependency: Refer to: r2094, r2095
Note: From the signal source set via the connector input, the corresponding lower 16 bits are converted.
p2099[0...1] together with r2094.0...15 and r2095.0...15 forms two connector-binector converters:
Connector input p2099[0] to binector output in r2094.0...15
Connector input p2099[1] to binector output in r2095.0...15
Description: Sets the signal source for the connector-binector converter.
A PZD receive word can be selected as signal source. The signals are available to be serially passed-on
(interconnection).
Dependency: Refer to: r2094, r2095
Note: From the signal source set via the connector input, the corresponding lower 16 bits are converted.
p2099[0...1] together with r2094.0...15 and r2095.0...15 forms two connector-binector converters:
Connector input p2099[0] to binector output in r2094.0...15
Connector input p2099[1] to binector output in r2095.0...15
p2098[0...1] Inverter connector-binector converter binector output / Con/bin outp inv
TM150, TM15DI_DO,
TM31
Can be changed: U, T Access level: 3
Data type: Unsigned16 Func. diagram: 2468
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 Inverted Not inverted -
01 Bit 1 Inverted Not inverted -
02 Bit 2 Inverted Not inverted -
03 Bit 3 Inverted Not inverted -
04 Bit 4 Inverted Not inverted -
05 Bit 5 Inverted Not inverted -
06 Bit 6 Inverted Not inverted -
07 Bit 7 Inverted Not inverted -
08 Bit 8 Inverted Not inverted -
09 Bit 9 Inverted Not inverted -
10 Bit 10 Inverted Not inverted -
11 Bit 11 Inverted Not inverted -
12 Bit 12 Inverted Not inverted -
13 Bit 13 Inverted Not inverted -
14 Bit 14 Inverted Not inverted -
15 Bit 15 Inverted Not inverted -
p2099[0...1] CI: Connector-binector converter signal source / Con/bin S_src
CU_DCP, DCP_CTRL Can be changed: U, T Access level: 3
Data type: Unsigned32 / Integer16 Func. diagram: 2460, 2481
Min Max Factory setting
- - 0
p2099[0...1] CI: Connector-binector converter signal source / Con/bin S_src
TM150, TM15DI_DO,
TM31
Can be changed: U, T Access level: 3
Data type: Unsigned32 / Integer16 Func. diagram: 2468
Min Max Factory setting
- - 0

Table of Contents