EasyManua.ls Logo

Siemens sinamics dcp - p0810 BI: Command data set selection CDS bit 0; CDS select., bit 0; p0819[0...2] Copy Drive Data Set DDS; Copy DDS; p0820[0...n] BI: Drive Data Set selection DDS bit 0; DDS select., bit 0; p0821[0...n] BI: Drive Data Set selection DDS bit 1; DDS select., bit 1

Siemens sinamics dcp
518 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS DCP
46 List Manual (LH21), 05/2016
Description: Sets the signal source to select the Command Data Set bit 0 (CDS bit 0).
Dependency: Refer to: r0050, r0836
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
Description: Copies one Drive Data Set (DDS) into another.
Index: [0] = Source Drive Data Set
[1] = Target Drive Data Set
[2] = Start copying procedure
Note: Procedure:
1. In Index 0, enter which drive data set is to be copied.
2. In Index 1, enter the drive data set data that is to be copied into.
3. Start copying: Set index 2 from 0 to 1.
p0819[2] is automatically set to 0 when copying is completed.
Description: Sets the signal source to select the Drive Data Set, bit 0 (DDS, bit 0).
Dependency: Refer to: r0051, r0837
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source to select the Drive Data Set, bit 1 (DDS, bit 1).
Dependency: Refer to: r0051, r0837
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Displays the status word for the drive data set changeover.
p0810 BI: Command data set selection CDS bit 0 / CDS select., bit 0
DCP_CTRL Can be changed: T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 8560
Min Max Factory setting
- - 0
p0819[0...2] Copy Drive Data Set DDS / Copy DDS
DCP_CTRL Can be changed: C2(15) Access level: 2
Data type: Unsigned8 Func. diagram: 8565
Min Max Factory setting
0 31 0
p0820[0...n] BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
DCP_CTRL Can be changed: C2(15), T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 8565, 8570
Min Max Factory setting
- - 0
p0821[0...n] BI: Drive Data Set selection DDS bit 1 / DDS select., bit 1
DCP_CTRL Can be changed: C2(15), T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 8565, 8570
Min Max Factory setting
- - 0
r0835.2 CO/BO: Data set changeover status word / DDS_ZSW
DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 8575
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
02 Internal parameter calculation active Yes No -

Table of Contents

Other manuals for Siemens sinamics dcp

Related product manuals