2 Parameters
2.2 List of parameters
SINAMICS DCP
64 List Manual (LH21), 05/2016
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
The parameter is set to the factory setting when the protocol is reselected.
Description: Sets the number of 16-bit words in the PZD part of the USS telegram for the field bus interface.
Dependency: Refer to: p2030
Note: The parameter is not influenced by setting the factory setting.
Description: Sets the number of 16-bit words in the PKW part of the USS telegram for the field bus interface.
Value: 0: PKW 0 words
3: PKW 3 words
4: PKW 4 words
127: PKW variable
Dependency: Refer to: p2030
Note: The parameter is not influenced by setting the factory setting.
Description: Displays the receive errors on the field bus interface (USS).
Index: [0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
Description: Sets the communication protocol for the field bus interface.
Value: 0: No protocol
1: USS
3: PROFIBUS
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
p2022 Field bus int USS PZD no. / Field bus USS PZD
CU_DCP Can be changed: T Access level: 2
Data type: Unsigned16 Func. diagram: 9310
Min Max Factory setting
0 16 2
p2023 Field bus int USS PKW no. / Field bus USS PKW
CU_DCP Can be changed: T Access level: 2
Data type: Integer16 Func. diagram: 9310
Min Max Factory setting
0 127 127
r2029[0...7] Field bus int error statistics / Field bus error
CU_DCP Can be changed: - Access level: 3
Data type: Unsigned32 Func. diagram: 9310
Min Max Factory setting
- - -
p2030 Field bus int protocol selection / Field bus protocol
CU_DCP Can be changed: T Access level: 1
Data type: Integer16 Func. diagram: -
Min Max Factory setting
0 3 3