2 Parameters
2.2 List of parameters
SINAMICS DCP
66 List Manual (LH21), 05/2016
Description: Sets the serial interface for the debug monitor.
With p2039 = 1, the serial interface COM2 (X179) is set.
Other values are not permitted.
Description: Sets the monitoring time to monitor the process data received via the fieldbus interface.
If no process data is received within this time, then an appropriate message is output.
Dependency: Refer to: F01910
Note: p2040 = 0:
Monitoring is de-activated.
Description: Sets the PROFIBUS Ident Number (PNO-ID).
SINAMICS can be operated with various identities on PROFIBUS. This allows the use of a PROFIBUS GSD that is
independent of the device (e.g. PROFIdrive VIK-NAMUR with Ident Number 3AA0 hex).
Value: 0: SINAMICS
1: VIK-NAMUR
Note: Every change only becomes effective after a POWER ON.
Description: Displays the PROFIdrive PZD state.
Dependency: Refer to: p2044
Note: When using the "setpoint failure" signal, the bus can be monitored and an application-specific response triggered
when the setpoint fails.
Description: Sets the delay time to initiate fault F01910 after a setpoint failure.
The time until the fault is initiated can be used by the application. This means that is is possible to respond to the
failure while the drive is still operational (e.g. emergency retraction).
p2039 Select debug monitor interface / Debug monit select
CU_DCP Can be changed: U, T Access level: 4
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
0 3 1
p2040 Fieldbus interface monitoring time / Fieldbus t_monit
CU_DCP Can be changed: U, T Access level: 3
Data type: FloatingPoint32 Func. diagram: 9310
Min Max Factory setting
0 [ms] 1999999 [ms] 100 [ms]
p2042 PROFIBUS Ident Number / PB Ident No.
CU_DCP Can be changed: T Access level: 3
Data type: Integer16 Func. diagram: -
Min Max Factory setting
0 1 0
r2043.0...2 BO: IF1 PROFIdrive PZD state / IF1 PD PZD state
CU_DCP Can be changed: - Access level: 3
Data type: Unsigned8 Func. diagram: 2410
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Setpoint failure Yes No -
02 Fieldbus oper Yes No -
p2044 IF1 PROFIdrive fault delay / IF1 PD fault delay
DCP_CTRL Can be changed: U, T Access level: 3
Data type: FloatingPoint32 Func. diagram: 2410
Min Max Factory setting
0 [s] 100 [s] 1 [s]