4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
490 List Manual (LH21), 05/2016
r50047[6]: Air intake temperature (in °C)
r50047[7]: Reference voltage +10 V (in Volt)
r50047[8]: Reference voltage -10 V (in Volt)
r50047[9]: Temperature power unit 3 (in °C)
Remedy: - check the ambient temperature and reduce if necessary.
- check the function of the device fan.
F60091 (N, A) Reference voltage P10 outside tolerance
Drive object: DCP_CTRL
Cause: Reference voltage P10 (+10 V) at terminal X177.31 outside tolerance.
The deviation is greater than +/-5 %.
Note:
r50047[1]: Temperature power unit 1 (in °C)
r50047[2]: Temperature power unit 2 (in °C)
r50047[3]: Temperature power supply module (in °C)
r50047[4]: Temperature mainboard module (in °C)
r50047[5]: Temperature CUD module (in °C)
r50047[6]: Air intake temperature (in °C)
r50047[7]: Reference voltage +10 V (in Volt)
r50047[8]: Reference voltage -10 V (in Volt)
r50047[9]: Temperature power unit 3 (in °C)
Remedy: Check the current load of the reference voltage P10 (X177.31).
F60092 (N, A) Reference voltage N10 outside tolerance
Drive object: DCP_CTRL
Cause: Reference voltage N10 (-10 V) at terminal X177.32 outside tolerance.
The deviation is greater than +/-5 %.
Note:
r50047[1]: Temperature power unit 1 (in °C)
r50047[2]: Temperature power unit 2 (in °C)
r50047[3]: Temperature power supply module (in °C)
r50047[4]: Temperature mainboard module (in °C)
r50047[5]: Temperature CUD module (in °C)
r50047[6]: Air intake temperature (in °C)
r50047[7]: Reference voltage +10 V (in Volt)
r50047[8]: Reference voltage -10 V (in Volt)
r50047[9]: Temperature power unit 3 (in °C)
Remedy: Check the current load of the reference voltage N10 (X177.32).
F60093 (N, A) Power supply P5 overloaded
Drive object: DCP_CTRL
Cause: Power supply P5 (+5 V) at connector X179.1 is overloaded.
Note:
r50047[1]: Temperature power unit 1 (in °C)
r50047[2]: Temperature power unit 2 (in °C)
r50047[3]: Temperature power supply module (in °C)
r50047[4]: Temperature mainboard module (in °C)
r50047[5]: Temperature CUD module (in °C)
r50047[6]: Air intake temperature (in °C)
r50047[7]: Reference voltage +10 V (in Volt)
r50047[8]: Reference voltage -10 V (in Volt)
r50047[9]: Temperature power unit 3 (in °C)
Remedy: Check the current load of the power supply P5 (X179.1).

Table of Contents

Other manuals for Siemens sinamics dcp

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens sinamics dcp and is the answer not in the manual?

Siemens sinamics dcp Specifications

General IconGeneral
BrandSiemens
Modelsinamics dcp
CategoryMedia Converter
LanguageEnglish

Related product manuals