SINAMICS DCP
List Manual (LH21), 05/2016
259
2 Parameters
2.2 List of parameters
Index 28: averaged current power unit 3 - setpoint current 1 [0.01 A]
Index 29: averaged current power unit 3 - actual current 1 [0.01 A]
Index 30: averaged current power unit 3 - setpoint current 2 [0.01 A]
Index 31: averaged current power unit 3 - actual current 2 [0.01 A]
Description: Display and connector output for the utilization of the TMS320 signal processors.
Index: [0] = TMS320 on CUD
[1] = TMS320 on mainboard
Description: Displays the reference voltages +10 V and -10 V.
Index: [0] = P10 (+10 V)
[1] = N10 (-10 V)
Dependency: Refer to: F60091, F60092
Note: For index 0:
A voltage value outside the permissible deviation triggers fault F60091.
For index 1:
A voltage value outside the permissible deviation triggers fault F60092.
Description: This parameter is only for internal Siemens troubleshooting.
Description: Displays the calibration values for the analog inputs/outputs on the Control Unit (CUD).
Description: Sets the trigger resolution for the trace.
Value: 0: No trigger for start
1: Immediately start trace
2: Start trace together with the commissioning tool
r50820[0...1] CO: TMS320 processor utilization / TMS320 util
DCP_CTRL Can be changed: - Access level: 3
Data type: FloatingPoint32 Func. diagram: 8054
Min Max Factory setting
- [%] - [%] - [%]
r50823[0...1] Electronic power supply voltage display / Electr supp U_disp
DCP_CTRL Can be changed: - Access level: 3
Data type: FloatingPoint32 Func. diagram: 8048
Min Max Factory setting
- [V] - [V] - [V]
r50827[0...1] Internal diagnostics / Int diag
DCP_CTRL Can be changed: - Access level: 4
Data type: Unsigned16 Func. diagram: 8054
Min Max Factory setting
- - -
r50829[0...55] CUD calibration values / CUD calib. val
DCP_CTRL Can be changed: - Access level: 4
Data type: Unsigned16 Func. diagram: 8054
Min Max Factory setting
- - -
p50831 Diagnostics memory trace control word / Diag_mem trace STW
DCP_CTRL Can be changed: U, T Access level: 2
Data type: Integer16 Func. diagram: 8056
Min Max Factory setting
0 2 0