2 Parameters
2.2 List of parameters
SINAMICS DCP
306 List Manual (LH21), 05/2016
Description: Displays the actual value of the current at side 2.
Dependency: Refer to: r55542
Description: Sets the offset for the "local" adjustment of the voltage actual value.
Index 0:
Adjustment of the voltage actual value at side 1
Index 1:
Adjustment of the voltage actual value at side 2
Index: [0] = Side 1
[1] = Side 2
Description: Sets the gain for the "local" adjustment of the voltage actual value.
Index 0:
Adjustment of the voltage actual value at side 1
Index 1:
Adjustment of the voltage actual value at side 2
Index: [0] = Side 1
[1] = Side 2
Description: Display and BICO output for the status of the power unit monitoring.
r55544 Actual value current side 2 / Act val I_S2
DCP_CTRL Can be changed: - Access level: 1
Data type: FloatingPoint32 Func. diagram: 6850
Min Max Factory setting
- [A] - [A] - [A]
p55545[0...1] Actual value voltage offset adjustment / ActVal U offs adj
DCP_CTRL Can be changed: U, T Access level: 3
Data type: FloatingPoint32 Func. diagram: 6850
Min Max Factory setting
-5.00 [%] 5.00 [%] 0.00 [%]
p55546[0...1] Actual value voltage gain adjustment / ActVal U gain adj
DCP_CTRL Can be changed: U, T Access level: 3
Data type: FloatingPoint32 Func. diagram: 6850
Min Max Factory setting
-5.00 [%] 5.00 [%] 0.00 [%]
r55550.0...15 CO/BO: Power unit monitoring status / PU monit status
DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 6855
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 IGBT1 desaturation occurred Yes No 6855
01 IGBT2 desaturation occurred Yes No 6855
02 IGBT3 desaturation occurred Yes No 6855
03 IGBT4 desaturation occurred Yes No 6855
04 IGBT5 desaturation occurred Yes No 6855
05 IGBT6 desaturation occurred Yes No 6855
06 IGBT7 desaturation occurred Yes No 6855
07 IGBT8 desaturation occurred Yes No 6855
08 Overcurrent has occurred in power unit 1 Yes No 6855
09 Overcurrent has occurred in power unit 2 Yes No 6855
10 Overvoltage has occurred at side 1. Yes No 6855
11 Overvoltage has occurred at side 2. Yes No 6855
12 Overtemperature has occurred at the AC Yes No 6855
13 Overtemperature has occurred at the BD Yes No 6855