Siemens sinamics dcp - p4082[0...1] BI: TM31 analog outputs invert signal source; TM31 AO inv s_src; p4083[0...1] TM31 analog outputs offset; TM31 AO offset; p4086 BI: TM15 DI;DO signal source for terminal DI;DO 16; TM15 D s_srcDI;DO16; p4087 BI: TM15 DI;DO signal source for terminal DI;DO 17; TM15 D s_srcDI;DO17

Siemens sinamics dcp
518 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS DCP
142 List Manual (LH21), 05/2016
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency: The unit of this parameter (V or mA) depends on the analog output type.
Refer to: p4076
Notice: This parameter is automatically overwritten when changing p4076 (type of analog outputs).
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the signal source to invert the analog output signals of Terminal Module 31 (TM31).
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Description: Sets the offset for the analog outputs of Terminal Module 31 (TM31).
The offset is added to the output signal after the scaling characteristic.
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency: The unit of this parameter (V or mA) depends on the analog input type.
Refer to: p4076
Note: This means, for example, the offset of a downstream isolating amplifier can be compensated.
Description: Sets the signal source for terminal DI/DO 16 (X522.2) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.16 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for terminal DI/DO 17 (X522.3) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.17 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for terminal DI/DO 18 (X522.4) of Terminal Module 15 (TM15).
p4082[0...1] BI: TM31 analog outputs invert signal source / TM31 AO inv s_src
TM31 Can be changed: U, T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 9572
Min Max Factory setting
- - 0
p4083[0...1] TM31 analog outputs offset / TM31 AO offset
TM31 Can be changed: U, T Access level: 1
Data type: FloatingPoint32 Func. diagram: 9572
Min Max Factory setting
-20.000 20.000 0.000
p4086 BI: TM15DI/DO signal source for terminal DI/DO 16 / TM15D s_srcDI/DO16
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9402
Min Max Factory setting
- - 0
p4087 BI: TM15DI/DO signal source for terminal DI/DO 17 / TM15D s_srcDI/DO17
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9402
Min Max Factory setting
- - 0
p4088 BI: TM15DI/DO signal source for terminal DI/DO 18 / TM15D s_srcDI/DO18
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9402
Min Max Factory setting
- - 0