Siemens sinamics dcp - r53030.0...1 CO;BO: CUD analog inputs wire break signal; CUD AI wire brk; r53130.0...1 CO;BO: Temperature monitoring external state; Temp_monit state; r53230.0...7 CO;BO: Fixed bit display; Fix bit displ; r53310.0...3 CO;BO: Parallel interface telegram monitoring state; Par_IF mon state

Siemens sinamics dcp
518 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS DCP
270 List Manual (LH21), 05/2016
Description: Display and connector output for the "Wire break" signal in the case of the CUD analog inputs.
Dependency: Refer to: F60046, F60047
Note: AI: Analog Input
Description: Display and BICO output for the state of the monitoring of the external temperature sensor (terminal X177.53-55).
Description: Display and BICO output for fixed bit 0 ... 7.
Dependency: Refer to: p50421, p50422, p50423, p50424, p50425, p50426, p50427, p50428
Description: Display and BICO output for the state of the telegram monitoring for the parallel interface.
r53030.0...1 CO/BO: CUD analog inputs wire break signal / CUD AI wire brk
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2075, 2080
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 AI "Main setpoint" wire break monitoring
responded
Yes No 2075
01 AI 1 (X177.27/28) wire break monitoring
responded
Yes No 2080
r53130.0...1 CO/BO: Temperature monitoring external state / Temp_monit state
DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 8030
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 External temperature alarm Yes No 8030
01 External temperature fault Yes No 8030
r53230.0...7 CO/BO: Fixed bit display / Fix bit displ
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 3100
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fixed bit 0 (p50421) High Low -
01 Fixed bit 1 (p50422) High Low -
02 Fixed bit 2 (p50423) High Low -
03 Fixed bit 3 (p50424) High Low -
04 Fixed bit 4 (p50425) High Low -
05 Fixed bit 5 (p50426) High Low -
06 Fixed bit 6 (p50427) High Low -
07 Fixed bit 7 (p50428) High Low -
r53310.0...3 CO/BO: Parallel interface telegram monitoring state / Par_IF mon state
DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 9350
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Telegram monitoring timeout - continuous
signal
Yes No 9350
01 Telegram monitoring timeout - pulse Yes No 9350
02 OFF1 from master 1 0 9350
03 Pulse enable from the master 1 0 9350