Description: Display and connector output for the "Wire break" signal in the case of the CUD analog inputs.
Dependency: Refer to: F60046, F60047
Note: AI: Analog Input
Description: Display and BICO output for the state of the monitoring of the external temperature sensor (terminal X177.53-55).
Description: Display and BICO output for fixed bit 0 ... 7.
Dependency: Refer to: p50421, p50422, p50423, p50424, p50425, p50426, p50427, p50428
Description: Display and BICO output for the state of the telegram monitoring for the parallel interface.
r53030.0...1 CO/BO: CUD analog inputs wire break signal / CUD AI wire brk
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2075, 2080
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 AI "Main setpoint" wire break monitoring
responded
Yes No 2075
01 AI 1 (X177.27/28) wire break monitoring
responded
Yes No 2080
r53130.0...1 CO/BO: Temperature monitoring external state / Temp_monit state
DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 8030
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 External temperature alarm Yes No 8030
01 External temperature fault Yes No 8030
r53230.0...7 CO/BO: Fixed bit display / Fix bit displ
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 3100
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fixed bit 0 (p50421) High Low -
01 Fixed bit 1 (p50422) High Low -
02 Fixed bit 2 (p50423) High Low -
03 Fixed bit 3 (p50424) High Low -
04 Fixed bit 4 (p50425) High Low -
05 Fixed bit 5 (p50426) High Low -
06 Fixed bit 6 (p50427) High Low -
07 Fixed bit 7 (p50428) High Low -
r53310.0...3 CO/BO: Parallel interface telegram monitoring state / Par_IF mon state
DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 9350
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Telegram monitoring timeout - continuous
signal
Yes No 9350
01 Telegram monitoring timeout - pulse Yes No 9350
02 OFF1 from master 1 0 9350
03 Pulse enable from the master 1 0 9350