2 Parameters
2.2 List of parameters
SINAMICS DCP
118 List Manual (LH21), 05/2016
Re bit 04:
The temperature in the component has exceeded the highest permissible limit. Check the ambient temperature /
control cabinet cooling.
Re bit 05:
A ground fault / inter-phase short-circuit was detected in the power cables or in the motor windings. Check the power
cable (connection). Check the motor.
Re bit 06:
The motor was operated outside the permissible limits (temperature, current, torque, ...). Check the load cycles and
limits that have been set. Check the ambient temperature / motor cooling.
Re bit 07:
The communication to the higher-level control system (internal coupling, PROFIBUS, PROFINET, ...) is faulted or
interrupted. Check the state of the higher-level control system. Check the communication connection/wiring. Check
the bus configuration / clock cycles.
Re bit 08:
A safety operation monitoring function (Safety) has detected an error.
Re bit 09:
When evaluating the encoder signals (track signals, zero marks, absolute values, ...) an illegal signal state was
detected. Check the encoder / state of the encoder signals. Observe the maximum frequencies.
Re bit 10:
The internal communication between the SINAMICS components is faulted or interrupted. Check the DRIVE-CLiQ
wiring. Ensure an EMC-compliant design. Observe the maximum permissible quantity structure / clock cycles.
Re bit 11:
The infeed is faulted or has failed. Check the infeed and the surroundings (line supply, filter, reactors, fuses, ...).
Check the closed-loop infeed control.
Re bit 15:
Group fault. Determine the precise cause of the fault using the commissioning tool.
Description: Displays the global status word for messages.
The appropriate bit is set if at least one message is present at the drive objects.
Note: The status bits are displayed with delay.
Description: Displays the drive object number of the initiating drive object for this fault as integer number.
Value = 63:
The fault was initiated by the drive object itself.
Dependency: Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136, r3120, r3122
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
r3114.9...11 CO/BO: Messages status word global / Msg ZSW global
CU_DCP Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
09 Group alarm present Yes No 8065
10 Group fault present Yes No 8060
11 Safety group message present Yes No -
r3115[0...63] Fault drive object initiating / F DO initiating
CU_DCP, DCP_CTRL Can be changed: - Access level: 3
Data type: Integer32 Func. diagram: -
Min Max Factory setting
- - -