2 Parameters
2.2 List of parameters
SINAMICS DCP
112 List Manual (LH21), 05/2016
Note: Re bit 03, 05, 07:
These bits are set if at least one fault/alarm occurs. Data is entered into the fault/alarm buffer with delay. This is the
reason that the fault/alarm buffer should only be read if, after "fault present" or "alarm present" has occurred, a
change in the buffer was also detected (r0944, r9744, r2121).
Re bit 06, 08:
These status bits are used for internal diagnostic purposes only.
Re bit 12, 11:
These status bits are used for the classification of internal alarm classes and are intended for diagnostic purposes
only on certain automation systems with integrated SINAMICS functionality.
Description: Displays the system runtime in days when the alarm occurred.
Dependency: Refer to: r2110, r2114, r2122, r2123, r2124, r2125, r2134, r2146, r3121, r3123
Notice: The time comprises r2145 (days) and r2123 (milliseconds).
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Description: Displays the system runtime in days when the alarm was cleared.
Dependency: Refer to: r2110, r2114, r2122, r2123, r2124, r2125, r2134, r2145, r3121, r3123
Notice: The time comprises r2146 (days) and r2125 (milliseconds).
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Description: Setting to delete the fault buffer of all existing drive objects.
Value: 0: Inactive
1: Start to delete the fault buffer of all drive objects
Dependency: Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136
Note: p2147 is automatically set to 0 after execution.
Description: Display and BICO output for the first status word of the monitoring functions.
r2145[0...63] Alarm time received in days / t_alarm recv days
All objects Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 8065
Min Max Factory setting
- - -
r2146[0...63] Alarm time removed in days / t_alarm res days
All objects Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 8065
Min Max Factory setting
- - -
p2147 Delete fault buffer of all drive objects / Del fault buffer
CU_DCP Can be changed: U, T Access level: 4
Data type: Integer16 Func. diagram: 8060
Min Max Factory setting
0 1 0
r2197.3...7 CO/BO: Status word monitoring 1 / ZSW monitor 1
DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 2534
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
03 n_act >= 0 Yes No 8011
07 Speed setp - act val deviation in tolerance
t_off
Yes No 8011