2 Parameters
2.2 List of parameters
SINAMICS DCP
246 List Manual (LH21), 05/2016
Description: Sets the scaling for analog input 1 (AI 1, X177.27/28) on the CUD.
The value indicates the percentage value for mapping an input voltage of 10 V or an input current of 20 mA at the
analog input.
Example:
p50711 = 90%
--> 10 V or 20 mA is scaled to 90%
--> 5 V or 10 mA is equivalent to 45%
Note: AI: Analog Input
Description: Sets the offset for analog input 1 (AI 1, X177.27/28) on the CUD.
Note: AI: Analog Input
Description: Sets the signal processing mode for analog input 1 (AI 1, X177.27/28) on the CUD.
Value: 0: Signal not influenced
1: Signal absolute value generation
2: Signal inverted
3: Signal absolute value generation inverted
Note: AI: Analog Input
Description: Sets the signal source for inverting the signal from analog input 1 (AI 1, X177.27/28) on the CUD.
1 signal: inversion
0 signal: no inversion
Note: AI: Analog Input
Description: Sets the time constant for smoothing the signal from analog input 1 (AI 1, X177.27/28) on the CUD.
Note: AI: Analog Input
p50711[0...n] CUD analog input 1 scaling / CUD AI 1 scal
DCP_CTRL Can be changed: U, T Access level: 3
Data type: FloatingPoint32 Func. diagram: 2080
Min Max Factory setting
-1000.0 [%] 1000.0 [%] 100.0 [%]
p50712 CUD analog input 1 offset / CUD AI 1 offs
DCP_CTRL Can be changed: U, T Access level: 3
Data type: FloatingPoint32 Func. diagram: 2080
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]
p50713 CUD analog input 1 signal processing / CUD AI 1 sig proc
DCP_CTRL Can be changed: T Access level: 3
Data type: Integer16 Func. diagram: 2080
Min Max Factory setting
0 3 0
p50714 BI: CUD analog input 1 inversion / CUD AI 1 inv
DCP_CTRL Can be changed: T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 2080
Min Max Factory setting
- - 0
p50715 CUD analog input 1 smoothing time constant / CUD AI 1 T
DCP_CTRL Can be changed: U, T Access level: 3
Data type: FloatingPoint32 Func. diagram: 2080
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]