2 Parameters
2.2 List of parameters
SINAMICS DCP
222 List Manual (LH21), 05/2016
Description: Sets the function for the component selected in p9210.
After initiating a function, the parameter is automatically reset again.
Example:
- Set the component number (p9210).
- Select the "flashing on" function (set p9211 = 1).
Value: -1: Select function
0: Flashing off
1: Flashing on
Dependency: Refer to: p9210
Notice: If a task cannot be executed (e.g. the component number in p9210 does not exist), the following applies:
- There is no negative feedback signal.
- The value is reset anyway.
Description: Supplies the number of entries in p9222.
Dependency: In p9221, the component Id is set whose statistic entries are to be displayed.
Refer to: p9221
Description: Selects the component Id whose statistics are to be displayed in p9222.
Description: Represents the statistic of acyclic Drive-CLiQ communication.
The component is preset in p9221.
The entry comprises the following elements:
Index 0: Parameter Id
Index 1: Number of messages sent.
Index 2: Minimum time of all acyclic requests referred to the parameter Id (index 0).
Index 3: Maximum time of all acyclic requests referred to the parameter Id (index 0).
Index 4: Average of all acyclic requests referred to the parameter Id (index 0).
The time unit is 10us.
p9211 Flash function / Flash fct.
CU_DCP Can be changed: U, T Access level: 3
Data type: Integer16 Func. diagram: -
Min Max Factory setting
-1 1 -1
r9220 Statistic number of entries / Statistic size
CU_DCP Can be changed: - Access level: 4
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
p9221 Statistic components Id / Statistic compId
CU_DCP Can be changed: T Access level: 4
Data type: Unsigned8 Func. diagram: -
Min Max Factory setting
0000 hex 00FF hex 0002 hex
r9222[0...n] Statistic Drive-CLiQ acyclic communication / Statistic
CU_DCP Can be changed: - Access level: 4
Data type: Unsigned32 Func. diagram: -
Min Max Factory setting
- - -