2 Parameters
2.2 List of parameters
SINAMICS DCP
50 List Manual (LH21), 05/2016
Description: Display and connector output for the control word of the sequence control.
Note: OC: Operating condition
Description: Displays the status word of the sequence control.
Note: Re bits 00, 01, 02, 04, 05, 06, 09:
For PROFIdrive, these signals are used for status word 1.
Description: Sets the PROFIBUS address for PROFIBUS interface (X126) on the Control Unit.
r0898.0...14 CO/BO: Control word sequence control / STW seq_ctrl
DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 2580
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 Yes No -
02 OC / OFF3 Yes No -
03 Operation enable Yes No -
04 Ramp-function generator enable Yes No -
05 Continue ramp-function generator Yes No -
06 Speed setpoint enable Yes No -
07 Command open brake Yes No -
08 Jog 1 Yes No -
09 Jog 2 Yes No -
10 Master ctrl by PLC Yes No -
12 Speed controller enable Yes No -
14 Command close brake Yes No -
r0899.0...15 CO/BO: Status word sequence control / ZSW seq_ctrl
DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 2585, 2750,
3150, 3151, 3152, 6810, 6830
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Rdy for switch on Yes No -
01 Ready Yes No -
02 Operation enabled Yes No -
03 Jog active Yes No -
04 No coasting active OFF2 inactive OFF2 active -
05 No Quick Stop active OFF3 inactive OFF3 active -
06 Switching on inhibited active Yes No -
07 Drive ready Yes No -
08 Controller enable Yes No -
09 Control request Yes No -
11 Pulses enabled Yes No -
12 Open holding brake Yes No -
13 Command close holding brake Yes No -
14 Pulse enable from the brake control Yes No -
15 Setpoint enable from the brake control Yes No -
p0918 PROFIBUS address / PB address
CU_DCP Can be changed: T Access level: 2
Data type: Unsigned16 Func. diagram: 1520, 2410
Min Max Factory setting
1 126 126