2 Parameters
2.2 List of parameters
Points along the characteristic:
r54040[0]: current value characteristic point 0
r54041[0]: power value characteristic point 0
r54040[1]: current value characteristic point 1
r54041[1]: power value characteristic point 1
...
r54040[31]: current value characteristic point 31
r54041[31]: power value characteristic point 31
Dependency: Refer to: r54041
Note: MPP: maximum power point (point along the characteristic with the maximum power)
Description: Displays the power values of the last PV array characteristic that was plotted.
Points along the characteristic:
r54040[0]: current value characteristic point 0
r54041[0]: power value characteristic point 0
r54040[1]: current value characteristic point 1
r54041[1]: power value characteristic point 1
...
r54040[31]: current value characteristic point 31
r54041[31]: power value characteristic point 31
Note: MPP: maximum power point (point along the characteristic with the maximum power)
Description: Sets the signal source for the voltage controller setpoint.
Description: Sets the ramp-up time/ramp-down time for the voltage controller setpoint.
The setpoint change is limited so that the setpoint can change by a maximum of 100 % in the time that is set here.
Description: Selects the signal source for the voltage actual value.
Value: 1: Actual value voltage side 1
2: Actual value voltage side 2
3: Actual value voltage inner side 1
4: Actual value voltage inner side 2
r54041[0...31] MPP tracker characteristic power / MPPT char P
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6700
Min Max Factory setting
- [kW] - [kW] - [kW]
p54100 CI: Voltage controller setpoint signal source / U_ctrl setp s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
- - 1
p54101 Voltage controller ramp-up time/ramp-down time / U_ctrl t_RU/t_RD
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
0.000 [s] 10.000 [s] 0.050 [s]
p54102 Voltage controller actual value selection / U_ctrl act val sel
DCP_CTRL Can be changed: T Access level: 2
Data type: Integer16 Func. diagram: 6818
Min Max Factory setting
1 4 3