4 Faults and alarms
4.2 List of faults and alarms
A40101 Alarm at DRIVE-CLiQ socket X101
Drive object: CU_DCP, TM150, TM15DI_DO, TM31
Cause: An alarm has occurred at the drive object at the DRIVE-CLiQ socket X101.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy: Evaluate the alarm buffer of the specified object.
A40102 Alarm at DRIVE-CLiQ socket X102
Drive object: TM150, TM15DI_DO, TM31
Cause: An alarm has occurred at the drive object at the DRIVE-CLiQ socket X102.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy: Evaluate the alarm buffer of the specified object.
A40103 Alarm at DRIVE-CLiQ socket X103
Drive object: TM150, TM15DI_DO, TM31
Cause: An alarm has occurred at the drive object at the DRIVE-CLiQ socket X103.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy: Evaluate the alarm buffer of the specified object.
A40104 Alarm at DRIVE-CLiQ socket X104
Drive object: TM150, TM15DI_DO, TM31
Cause: An alarm has occurred at the drive object at the DRIVE-CLiQ socket X104.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy: Evaluate the alarm buffer of the specified object.
A40105 Alarm at DRIVE-CLiQ socket X105
Drive object: TM150, TM15DI_DO, TM31
Cause: An alarm has occurred at the drive object at the DRIVE-CLiQ socket X105.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy: Evaluate the alarm buffer of the specified object.
F40799 CX32: Configured transfer end time exceeded
Drive object: TM150, TM15DI_DO, TM31
Cause: The configured transfer end time when transferring the cyclic actual values was exceeded.
Remedy: - carry out a POWER ON (power off/on) for all components.
- contact the Hotline.
F40801 CX32 DRIVE-CLiQ: Sign-of-life missing
Drive object: TM150, TM15DI_DO, TM31
Cause: A DRIVE-CLiQ communications error has occurred from the Control Unit to the controller extension involved.
Fault cause:
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - carry out a POWER ON (power off/on).
- replace the component involved.