Siemens sinamics dcp - p9484 BICO interconnections search signal source; BICO S_src srch; r9485 BICO interconnections signal source search count; BICO S_src srchQty; r9486 BICO interconnections signal source search first index; BICO S_src srchIdx; r9490 Number of BICO interconnections to other drives; Qty BICO to drive

Siemens sinamics dcp
518 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS DCP
226 List Manual (LH21), 05/2016
Description: Sets the signal source (BO/CO parameter, BICO coded) to search in the signal sinks.
The question is answered:
How often is a connection made to a signal source in the drive object and from which index are these
interconnections saved (r9482 and r9483)?
Dependency: Refer to: r9481, r9482, r9483, r9485, r9486
Description: Displays the number of BICO interconnections to the signal sink being searched for.
Dependency: Refer to: r9481, r9482, r9483, p9484, r9486
Note: The signal source to be searched is set in p9484 (BICO-coded).
The search result is contained in r9482 and r9483 and is specified by the count (r9485) and the first index (r9486).
Description: Displays the first index of the signal source being searched for.
Dependency: Refer to: r9481, r9482, r9483, p9484, r9485
Note: The signal source to be searched is set in p9484 (BICO-coded).
The search result is contained in r9482 and r9483 and is specified by the count (r9485) and the first index (r9486).
Description: Displays the number of signal sources from this drive to other drives/drive objects (Binector Output/Connector
Output, BO/CO).
Dependency: Refer to: r9491, r9492, p9493
Description: Displays the signal receiver list (Binector Input/Connector Input, BI/CI) for the first interconnections between this
drive and other drives/drive objects.
Dependency: Refer to: r9490, r9492, p9493
Notice: A drive cannot be deleted if this list is not empty!
Otherwise, another drive would continue to attempt to read a signal from a drive that no longer existed.
Note: All indices of r9491 to p9493 designate the same interconnection.
r9491[x] contains the signal receiver and r9492[x] the matching signal source; p9493[x] can be set to modify the
interconnection.
p9484 BICO interconnections search signal source / BICO S_src srch
All objects Can be changed: U, T Access level: 3
Data type: Unsigned32 Func. diagram: -
Min Max Factory setting
0 4294967295 0
r9485 BICO interconnections signal source search count / BICO S_src srchQty
All objects Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
r9486 BICO interconnections signal source search first index / BICO S_src srchIdx
All objects Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
r9490 Number of BICO interconnections to other drives / Qty BICO to drive
All objects Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
r9491[0...9] BI/CI of BICO interconnections to other drives / BI/CI to drive
All objects Can be changed: - Access level: 3
Data type: Unsigned32 Func. diagram: -
Min Max Factory setting
- - -