Siemens sinamics dcp - r54994[0...31] CO: Mainboard diagnostics EEPROM display values; EEPROM disp_values; p55050 CI: Voltage controller setpoint signal source; I_set s_src; p55055 Current setpoint ramp-up time;ramp-down time; I_set t_RU;t_RD; p55056 Current setpoint minimum threshold; I_set min thresh

Siemens sinamics dcp
518 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS DCP
282 List Manual (LH21), 05/2016
Value: 0: Deactivated
1: Activated
Dependency: Refer to: p54990, p54991, p54992, r54994
Description: Display and connector output for the values in the EEPROM on the mainboard.
Dependency: Refer to: p54990, p54991, p54992, p54993
Description: Sets the signal source for the current setpoint.
Description: Sets the ramp-up time/ramp-down time for the current setpoint.
The current setpoint change is limited so that the setpoint can change by a maximum of 100 % in the time that is set
here.
Description: Sets the absolute value of the minimum current setpoint.
Description: Sets the significance for the setpoint.
Value: 10: Reactor current
11: Current side 1
12: Current side 2
20: Power
Note: The current actual value sensing in SINAMICS DCP measures the reactor current.
The specified setpoint is converted into a reactor current setpoint and this is used for the closed-loop current control.
For value = 10:
Reactor current setpoint = setpoint (no conversion)
For value = 11:
The current at side 1 is specified as setpoint.
If U1 <= U2: reactor current setpoint = setpoint (no conversion)
If U1 > U2: reactor current setpoint = setpoint * U1/U2
r54994[0...31] CO: Mainboard diagnostics EEPROM display values / EEPROM disp_values
DCP_CTRL Can be changed: - Access level: 4
Data type: Unsigned8 Func. diagram: 8055
Min Max Factory setting
- - -
p55050 CI: Voltage controller setpoint signal source / I_set s_src
DCP_CTRL Can be changed: U, T Access level: 2
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6805
Min Max Factory setting
- - 2050[1]
p55055 Current setpoint ramp-up time/ramp-down time / I_set t_RU/t_RD
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6805
Min Max Factory setting
0.000 [s] 10.000 [s] 0.050 [s]
p55056 Current setpoint minimum threshold / I_set min thresh
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6805
Min Max Factory setting
0.00 [%] 50.00 [%] 0.40 [%]
p55060 Current setpoint significance / I_set significance
DCP_CTRL Can be changed: U, T Access level: 1
Data type: Integer16 Func. diagram: 6806
Min Max Factory setting
10 20 11