2 Parameters
2.2 List of parameters
SINAMICS DCP
56 List Manual (LH21), 05/2016
Description: The parameter is used to initiate a reset of the parameters on Terminal Module 15 (TM15).
The sampling time p4099 is not reset if in so doing a conflict occurs with the basic clock cycle.
Parameter p0151 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976).
Value: 0: Inactive
1: Start a parameter reset
100: Start a BICO interconnection reset
Dependency: Refer to: p0010
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note: A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Description: The parameter is used to initiate a reset of the parameters on Terminal Module 31 (TM31).
The sampling time p4099 is not reset if in so doing a conflict occurs with the basic clock cycle.
Parameter p0151 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976).
Value: 0: Inactive
1: Start a parameter reset
100: Start a BICO interconnection reset
Dependency: Refer to: p0010
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note: A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Description: Setting to save the parameter of the particular drive object in the non-volatile memory.
When saving, only the adjustable parameters intended to be saved are taken into account.
Value: 0: Inactive
1: Save drive object
Dependency: Refer to: p0977, r3996
Caution: If a memory card (optional) is inserted, the following applies:
The parameters are also saved on the card and therefore overwrite any existing data!
Notice: The Control Unit power supply may only be powered down after data has been saved (i.e. after data save has been
started, wait until the parameter again has the value 0).
Writing to parameters is inhibited while saving.
The progress while saving is displayed in r3996.
p0970 TM15DI/DO reset parameter / TM15D par reset
TM15DI_DO Can be changed: C2(30) Access level: 2
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
0 100 0
p0970 TM31 reset parameters / TM31 par reset
TM31 Can be changed: C2(30) Access level: 2
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
0 100 0
p0971 Save drive object parameters / Drv_obj par save
CU_DCP, DCP_CTRL Can be changed: U, T Access level: 1
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
0 1 0