2 Parameters
2.2 List of parameters
SINAMICS DCP
262 List Manual (LH21), 05/2016
Description: Sets the signal source to initiate fault F60014 - "Telegram monitoring time expired".
The fault is triggered for a 1 signal.
Description: Displays the diagnostics information for the parallel interface.
Index: [0] = Telegrams transmitted without errors
[1] = Telegrams received without errors
[2] = Transmission error
[3] = Receive error
[4] = Timeouts
Note: The counters are reset to 0 at POWER ON.
The counters restart at 0 after reaching a value of 65535 (overflow).
Description: Displays the activities of the individual devices connected to the parallel interface.
Note: The counters are reset to 0 at POWER ON.
The counters restart at 0 after reaching a value of 65535 (overflow).
Description: Displays the CAN diagnostic information for the parallel interface.
p51808 BI: Parallel interface signal source for F60014 / P_IF F60014 s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / Binary Func. diagram: 9350
Min Max Factory setting
- - 53310.0
r51809[0...4] Parallel interface diagnostics information / Par_IF diag info
DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 9350
Min Max Factory setting
- - -
r51810 Parallel interface activity display / Par_IF act disp
DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 9350
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Station 1 transmitting data Yes No 9350
01 Station 2 transmitting data Yes No 9350
02 Station 3 transmitting data Yes No 9350
03 Station 4 transmitting data Yes No 9350
04 Station 5 transmitting data Yes No 9350
05 Station 6 transmitting data Yes No 9350
06 Station 7 transmitting data Yes No 9350
07 Station 8 transmitting data Yes No 9350
08 Station 9 transmitting data Yes No 9350
09 Station 10 transmitting data Yes No 9350
10 Station 11 transmitting data Yes No 9350
11 Station 12 transmitting data Yes No 9350
12 Station 13 transmitting data Yes No 9350
13 Station 14 transmitting data Yes No 9350
14 Station 15 transmitting data Yes No 9350
15 Station 16 transmitting data Yes No 9350
r51811 Parallel interface CAN diagnostics information / Par_IF CAN diag
DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 9350
Min Max Factory setting
- - -