Siemens sinamics dcp - r54103 CO: Voltage controller setpoint after the ramp-function generator; U_ctr U_set af RFG; p54105 BI: Voltage controller activation signal source; U_ctrl act s_src; p54121 Voltage controller actual value rate time; U_ctr act val Tv; p54122 Voltage controller actual value smoothing time constant; U_ctrl act val T

Siemens sinamics dcp
518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS DCP
276 List Manual (LH21), 05/2016
Description: Display and connector output for the voltage setpoint after the ramp-function generator.
Description: Sets the signal source for activating the voltage controller.
Description: Sets the rate time in the voltage actual value channel of the voltage controller.
Description: Sets the smoothing time constant for the voltage actual value channel of the voltage controller.
Description: Sets the width of the dead range in the setpoint-actual value difference channel for the "DC link buffering" function.
Dependency: Refer to: p54146
Note: The set value refers to the rated voltage of the SINAMICS DCP.
Description: Sets the proportional gain Kp for the voltage controller.
Description: Sets the integral time Tn for the voltage controller.
r54103 CO: Voltage controller setpoint after the ramp-function generator / U_ctr U_set af RFG
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
- [%] - [%] - [%]
p54105 BI: Voltage controller activation signal source / U_ctrl act s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / Binary Func. diagram: 6818
Min Max Factory setting
- - 0
p54121 Voltage controller actual value rate time / U_ctr act val Tv
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
0.00 [ms] 100.00 [ms] 10.00 [ms]
p54122 Voltage controller actual value smoothing time constant / U_ctrl act val T
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
0.00 [ms] 100.00 [ms] 2.00 [ms]
p54124 Voltage controller DC link buffering dead range / U_ctr VDC dead rng
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
0.00 [%] 100.00 [%] 0.00 [%]
p54125 Voltage controller proportional gain / U_ctrl Kp
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
0.001 30.000 2.000
p54126 Voltage controller integral time / U_ctrl Tn
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
0.01 [ms] 1000.00 [ms] 0.30 [ms]