2 Parameters
2.2 List of parameters
SINAMICS DCP
288 List Manual (LH21), 05/2016
Description: Sets the lower threshold value for the undervoltage on side 1.
The reactor current is reduced to zero from this value.
Description: Sets the upper threshold value for the undervoltage on side 1.
The reactor current is reduced from this value.
Description: Sets the lower threshold value for the overvoltage on side 1.
The reactor current is reduced from this value.
Description: Sets the upper threshold value for the overvoltage on side 1.
The reactor current is reduced to zero from this value.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Positive current limiting active Yes No 6810
01 Negative current limiting active Yes No 6810
02 Voltage in the undervoltage range Yes No 6810
03 Voltage in the normal voltage range below
rated voltage
Yes No 6810
04 Voltage in the normal voltage range above
rated voltage
Yes No 6810
05 Voltage in the overvoltage range Yes No 6810
06 Voltage in illegal range Yes No 6810
07 PV flying connection active Yes No 6810
08 Lower voltage limit reached on side 1 Yes No 6812
09 Upper voltage limit reached on side 1 Yes No 6812
10 Upper voltage limit reached on side 2 Yes No 6812
11 Lower voltage limit reached on side 2 Yes No 6812
12 Dynamic voltage limit reached on side 1 Yes No 6817
13 Dynamic voltage limit reached on side 2 Yes No 6817
14 PWM limited reached Yes No 6825
15 Main current controller has reached its limit Yes No 6820
p55130 Limiting side 1 undervoltage lower / Lim S1 U_under low
DCP_CTRL Can be changed: U, T Access level: 1
Data type: FloatingPoint32 Func. diagram: 6812
Min Max Factory setting
0 [V] 1500 [V] 50 [V]
p55131 Limiting side 1 undervoltage upper / Lim S1 U_under up
DCP_CTRL Can be changed: U, T Access level: 1
Data type: FloatingPoint32 Func. diagram: 6812
Min Max Factory setting
0 [V] 1500 [V] 100 [V]
p55132 Limiting side 1 overvoltage lower / Lim S1 U_over low
DCP_CTRL Can be changed: U, T Access level: 1
Data type: FloatingPoint32 Func. diagram: 6812
Min Max Factory setting
0 [V] 1500 [V] 800 [V]
p55133 Limiting side 1 overvoltage upper / Lim S1 U_over up
DCP_CTRL Can be changed: U, T Access level: 1
Data type: FloatingPoint32 Func. diagram: 6812
Min Max Factory setting
0 [V] 1500 [V] 1000 [V]