Siemens sinamics dcp - p55350 Precharging operating mode; Prechg_mode; p55352 CI: Precharging target value signal source; Pre targ_val s_src; p55355[0...1] Precharging wait time after precharging contactor close; Prchg t prchg_cont; p55356[0...1] Precharging wait time after DC contactor closed; Prechrg t DC cont

Siemens sinamics dcp
518 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS DCP
296 List Manual (LH21), 05/2016
Description: Sets the operating mode for resistor precharging.
Value: 1: Resistor precharging side 1, up pulsing on side 2
2: Resistor precharging side 2, up pulsing on side 1
3: Resistor precharging both sides (side 1, side 2)
4: Resistor precharging both sides (side 2, side 1)
Dependency: Refer to: p55110
Refer to: F60058
Note: It is not permissible to set p55350 < 3 - and at the same time set p55110 > 0
Description: Sets the signal source for the target value for precharging using the "pulsing up" technique.
When precharging, the voltage is pulsed up to this target value.
Description: Sets the wait time for closing the precharging contactor.
Index: [0] = Side 1
[1] = Side 2
Description: Sets the wait time for closing the DC contactors.
Index: [0] = Side 1
[1] = Side 2
Description: Sets the tolerance for reaching the setpoint voltage for resistor or pulsing up precharging.
Index: [0] = Side 1
[1] = Side 2
p55350 Precharging operating mode / Prechg_mode
DCP_CTRL Can be changed: U, T Access level: 1
Data type: Integer16 Func. diagram: 6835
Min Max Factory setting
1 4 3
p55352 CI: Precharging target value signal source / Pre targ_val s_src
DCP_CTRL Can be changed: U, T Access level: 2
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6835
Min Max Factory setting
- - 2050[2]
p55355[0...1] Precharging wait time after precharging contactor close / Prchg t prchg_cont
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6835
Min Max Factory setting
0 [ms] 1000000 [ms] 100 [ms]
p55356[0...1] Precharging wait time after DC contactor closed / Prechrg t DC cont
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6835
Min Max Factory setting
0 [ms] 1000000 [ms] 100 [ms]
p55357[0...1] Precharging setpoint voltage tolerance / Prechrg U_set tol
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6835
Min Max Factory setting
0.0 [%] 20.0 [%] 3.0 [%]