2 Parameters
2.2 List of parameters
SINAMICS DCP
244 List Manual (LH21), 05/2016
Dependency: The parameter is only valid for the following temperature sensors with a continuous characteristic:
- KTY84 (p50490 = 1)
- PT100 (p50490 = 6).
- NTC thermistor K227 (p50490 = 7)
- PT1000 (p50490 = 8)
Description: Sets the fault threshold for monitoring the external temperature (terminal X177.53-55).
Dependency: The parameter is only valid for the following temperature sensors with a continuous characteristic:
- KTY84 (p50490 = 1)
- PT100 (p50490 = 6).
- NTC thermistor K227 (p50490 = 7)
- PT1000 (p50490 = 8)
Description: Sets the type for analog input 0 (AI 0, X177.25/26) on the CUD.
Value: 0: Bipolar voltage input (-10 V ... +10 V)
1: Bipolar current input (-20 mA ... +20 mA)
2: Unipolar current input monitored (+4 mA ... +20 mA)
Note: AI: Analog Input
Description: Sets the scaling for analog input 0 (AI 0, X177.25/26) on the CUD.
The value indicates the percentage value for mapping an input voltage of 10 V or an input current of 20 mA at the
analog input.
Example:
p50701 = 90%
--> 10 V or 20 mA is scaled to 90%
--> 5 V or 10 mA is equivalent to 45%
Note: AI: Analog Input
Description: Sets the offset for analog input 0 (AI 0, X177.25/26) on the CUD.
Note: AI: Analog Input
p50492 Temperature monitoring external fault threshold / Ext temp F thresh
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 8030
Min Max Factory setting
0 [°C] 200 [°C] 0 [°C]
p50700 CUD analog input 0 type / CUD AI 0 type
DCP_CTRL Can be changed: T Access level: 3
Data type: Integer16 Func. diagram: 2075
Min Max Factory setting
0 2 0
p50701[0...n] CUD analog input 0 scaling / CUD AI 0 scal
DCP_CTRL Can be changed: U, T Access level: 3
Data type: FloatingPoint32 Func. diagram: 2075
Min Max Factory setting
-1000.0 [%] 1000.0 [%] 100.0 [%]
p50702 CUD analog input 0 offset / CUD AI 0 offs
DCP_CTRL Can be changed: U, T Access level: 3
Data type: FloatingPoint32 Func. diagram: 2075
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]