Siemens sinamics dcp - p4031 BI: TM15 DI;DO signal source for terminal DI;DO 1; TM15 D S_src DI;DO1; p4031 BI: TM31 signal source for terminal DO 1; TM31 s_src DO 1; p4032 BI: TM15 DI;DO signal source for terminal DI;DO 2; TM15 D S_src DI;DO2; p4033 BI: TM15 DI;DO signal source for terminal DI;DO 3; TM15 D S_src DI;DO3

Siemens sinamics dcp
518 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS DCP
130 List Manual (LH21), 05/2016
Description: Sets the signal source for terminal DI/DO 1 (X520.3) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.1 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for the digital output DO 1 (X542.4, X542.5, X542.6) of Terminal Module 31 (TM31).
Digital output 1 of TM31 is a relay output.
If the signal at the binector input p4031 is low, then terminal COM 1 (X542.5) is connected to NC 1 (X542.4). This
connection also matches the mechanical quiescent setting of the relay.
If the signal at the binector input p4031 is high, then terminal COM 1 (X542.5) is connected to NO 1 (X542.6).
Note: DO: Digital Output
NC: Normally Closed contact
NO: Normally Open contact
Description: Sets the signal source for terminal DI/DO 2 (X520.4) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.2 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for terminal DI/DO 3 (X520.5) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.3 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for terminal DI/DO 4 (X520.6) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.4 = 1).
DI/DO: Bidirectional Digital Input/Output
p4031 BI: TM15DI/DO signal source for terminal DI/DO 1 / TM15D S_src DI/DO1
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9400
Min Max Factory setting
- - 0
p4031 BI: TM31 signal source for terminal DO 1 / TM31 s_src DO 1
TM31 Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9549, 9556
Min Max Factory setting
- - 0
p4032 BI: TM15DI/DO signal source for terminal DI/DO 2 / TM15D S_src DI/DO2
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9400
Min Max Factory setting
- - 0
p4033 BI: TM15DI/DO signal source for terminal DI/DO 3 / TM15D S_src DI/DO3
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9400
Min Max Factory setting
- - 0
p4034 BI: TM15DI/DO signal source for terminal DI/DO 4 / TM15D S_src DI/DO4
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9400
Min Max Factory setting
- - 0