2 Parameters
2.2 List of parameters
SINAMICS DCP
158 List Manual (LH21), 05/2016
Description: Setting to activate/deactivate the filter to smooth the temperature signal for the Terminal Module 150 (TM150).
The smoothing is realized with a 1st order lowpass filter
The effective smoothing time constant depends on the number of channels that are simultaneously active and is
displayed in r4120.
Value: 0: Filter deactivated
1: Filter activated
Index: [0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
[6] = Temperature channel 6
[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency: Refer to: r4120
Description: Displays the smoothing time constant for the temperature filter for Terminal Module 150 (TM150).
Dependency: Refer to: r4105, p4111, r4112, r4113
Note: The time constant lies in the range from 80 to 1000 ms and depends on the number of channels that are
simultaneously active.
Description: Sets the rated line frequency for the filter to skip the line frequency for Terminal Module 150 (TM150).
Value: 0: 50 Hz
1: 60 Hz
Description: Trace functionality for OEM encoder manufacturers.
Index: [0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
p4119[0...11] TM150 activate/deactivate smoothing / TM150 smooth act
TM150 Can be changed: T Access level: 1
Data type: Integer16 Func. diagram: 9626, 9627
Min Max Factory setting
0 1 0
r4120 TM150 temperature filter time constant / TM150 temp_filt T
TM150 Can be changed: - Access level: 1
Data type: Unsigned16 Func. diagram: 9626, 9627
Min Max Factory setting
- [ms] - [ms] - [ms]
p4121 TM150 filter rated line frequency / TM150 filt f_line
TM150 Can be changed: T Access level: 1
Data type: Integer16 Func. diagram: 9626, 9627
Min Max Factory setting
0 1 0
p4641[0...2] OEM encoder diagnostic signal selection / OEM enc diag sel
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
0 65535 0