4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
482 List Manual (LH21), 05/2016
35 (= 23 hex):
Receive error: The telegram buffer memory contains an error.
66 (= 42 hex):
Send error: The telegram buffer memory contains an error.
67 (= 43 hex):
Send error: The telegram buffer memory contains an error.
96 (= 60 hex):
Response received too late during runtime measurement.
97 (= 61 hex):
Time taken to exchange characteristic data too long.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
F40895 CX32 DRIVE-CLiQ (CU): Cyclic data transfer error
Drive object: TM150, TM15DI_DO, TM31
Cause: A DRIVE-CLiQ communications error has occurred from the controller extension involved to the Control Unit.
Fault cause:
11 (= 0B hex):
Synchronization error during alternating cyclic data transfer.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: Carry out a POWER ON (power off/on).
A50001 (F) PN/COMM BOARD: Configuration error
Drive object: All objects
Cause: CBE20:
A PROFINET controller attempts to establish a connection using an incorrect configuring telegram. The "Shared
Device" function has been activated (p8829 = 2).
Alarm value (r2124, interpret decimal):
10: A CPU sends a PROFIsafe telegram.
11: F CPU sends a PZD telegram.
12: F CPU without an A CPU.
13: F CPU with more PROFIsafe subslots than activated with p9601.3.
14: F CPU with fewer PROFIsafe subslots than activated with p9601.3.
15: PROFIsafe telegram of the F-CPU does not match the setting in p60022.
Remedy: CBE20:
Check the configuration of the PROFINET controllers as well as the p8829 and p9601.3 setting.
A50002 (F) COMM BOARD: Alarm 2
Drive object: CU_DCP, TM150, TM15DI_DO, TM31
Cause: CBE20 SINAMICS Link:
A specific telegram word (send) is being used twice.
Alarm value (r2124, interpret decimal):
Telegram word used twice
See also: p8871 (SINAMICS Link send telegram word PZD)
Remedy: CBE20 SINAMICS Link:
Correct the parameter assignment.
See also: p8871 (SINAMICS Link send telegram word PZD)