SINAMICS DCP
List Manual (LH21), 05/2016
489
4 Faults and alarms
4.2 List of faults and alarms
Note for fault value = 3, 6:
r50047[1]: 1st character of the Z options
r50047[2]: 2nd character of the Z options
...
r50047[30]: 30th character of the Z options
Note for fault value = 9:
r50047[1]: Operating state
Remedy: Send the device to an authorized repair shop.
Note:
MLFB: Machine-readable product code
A60080 (F, N) Alarm power unit temperature exceeded
Drive object: DCP_CTRL
Cause: The temperature in the power unit has exceeded the internally specified alarm threshold.
Fault value (r0949, interpret decimal):
1: Power unit 1.
2: Power unit 2.
Note:
r50047[1]: Temperature power unit 1 (in °C)
r50047[2]: Temperature power unit 2 (in °C)
r50047[3]: Temperature power supply module (in °C)
r50047[4]: Temperature mainboard module (in °C)
r50047[5]: Temperature CUD module (in °C)
r50047[6]: Air intake temperature (in °C)
r50047[7]: Reference voltage +10 V (in Volt)
r50047[8]: Reference voltage -10 V (in Volt)
r50047[9]: Temperature power unit 3 (in °C)
Remedy: - check the ambient temperature and reduce if necessary.
- check the function of the device fan.
A60081 (F, N) Alarm CUD module temperature exceeded
Drive object: DCP_CTRL
Cause: The temperature of the Control Unit (CUD) has exceeded 90 °C.
Note:
r50047[1]: Temperature power unit 1 (in °C)
r50047[2]: Temperature power unit 2 (in °C)
r50047[3]: Temperature power supply module (in °C)
r50047[4]: Temperature mainboard module (in °C)
r50047[5]: Temperature CUD module (in °C)
r50047[6]: Air intake temperature (in °C)
r50047[7]: Reference voltage +10 V (in Volt)
r50047[8]: Reference voltage -10 V (in Volt)
r50047[9]: Temperature power unit 3 (in °C)
Remedy: - check the ambient temperature and reduce if necessary.
- check the function of the device fan.
F60090 (N, A) Fault CUD module temperature exceeded
Drive object: DCP_CTRL
Cause: The temperature on the Control Unit (CUD) has exceeded 95 °C.
Note:
r50047[1]: Temperature power unit 1 (in °C)
r50047[2]: Temperature power unit 2 (in °C)
r50047[3]: Temperature power supply module (in °C)
r50047[4]: Temperature mainboard module (in °C)
r50047[5]: Temperature CUD module (in °C)