2 Parameters
2.2 List of parameters
SINAMICS DCP
148 List Manual (LH21), 05/2016
Note: The changed sampling time is immediately effective after a completed sub-boot (p0009 -> 0).
Parameter p4099[0] must never be equal to zero.
Description: Sets the sensor type for Terminal Module 150 (TM150)
This means that the temperature sensor type is selected and the evaluation is switched in.
Value: 0: Evaluation disabled
1: PTC thermistor
2: KTY84
4: Bimetallic NC contact
5: PT100
6: PT1000
Index: [0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
[6] = Temperature channel 6
[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Notice: For p4102[0...23] = 251 °C, evaluation of the corresponding threshold is deactivated.
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[0...11] = 1, 4), the following applies:
To activate the corresponding alarm or fault, p4102[0...23] must be set <= 250 °C.
Note: The temperature sensors are connected to the following terminals:
X531 = channel 0 (for 2x2 wire evaluation, additionally channel 6)
X532 = channel 1 (for 2x2 wire evaluation, additionally channel 7)
X533 = channel 2 (for 2x2 wire evaluation, additionally channel 8)
X534 = channel 3 (for 2x2 wire evaluation, additionally channel 9)
X535 = channel 4 (for 2x2 wire evaluation, additionally channel 10)
X536 = channel 5 (for 2x2 wire evaluation, additionally channel 11)
Details on the wiring are included in the parameter description for p4108.
Description: Sets the sensor type for Terminal Module 31 (TM31)
This means that the temperature sensor type is selected and the evaluation is switched in.
Value: 0: Evaluation disabled
1: PTC thermistor
2: KTY84
Notice: For p4102[0...1] = 251 °C, evaluation of the corresponding threshold is deactivated.
For sensor type "PTC thermistor" (p4100 = 1), the following applies:
To activate the corresponding alarm or fault, p4102[0...1] must be set <= 250 °C.
Note: The temperature sensor is connected at terminals X522.7(+) and X522.8(-).
p4100[0...11] TM150 sensor type / TM150 sensor type
TM150 Can be changed: T Access level: 1
Data type: Integer16 Func. diagram: 9626, 9627
Min Max Factory setting
0 6 5
p4100 TM31 sensor type / TM31 sensor type
TM31 Can be changed: T Access level: 1
Data type: Integer16 Func. diagram: 9576
Min Max Factory setting
0 2 0