2 Parameters
2.2 List of parameters
SINAMICS DCP
286 List Manual (LH21), 05/2016
Description: Display and connector output for the output of the load cycle monitoring.
This signal indicates the percentage of the permissible overload duration that has already been utilized.
Description: Sets the installation altitude at which the device is operated.
The current and voltage are reduced for an installation altitude exceeding 2000 m.
Description: Sets the reduction values for the fixed temperature thresholds.
The values set here are added to the corresponding temperature thresholds.
The thresholds can only be reduced as only negative values can be set.
Index 0:
Reduction of the threshold for derating dependent on the ambient temperature.
This means that the threshold for A60502 is also reduced (see function diagrams 6808 and 6810).
Index 1:
Reduction of the threshold for derating dependent on the heat sink temperature.
This means that the threshold for A60080 is also reduced (see function diagram 8048).
Index: [0] = Ambient temperature
[1] = Heat sink temperature
Description: Sets the response when the maximum permissible heat sink temperature is exceeded.
Value: 1: Pulse frequency and current reduction
2: Current reduction
3: Pulse frequency reduction
4: Immediate shutdown with fault
Description: Sets the minimum voltage.
Operation is only possible if the voltages on side 1 and side 2 continuously exceed the value set here.
r55091 CO: Dynamic overload load cycle monitoring signal / Dyn overload t_sig
DCP_CTRL Can be changed: - Access level: 3
Data type: FloatingPoint32 Func. diagram: 6808
Min Max Factory setting
- [%] - [%] - [%]
p55100 Installation altitude / Install_altitude
DCP_CTRL Can be changed: U, T Access level: 1
Data type: FloatingPoint32 Func. diagram: 6810
Min Max Factory setting
0 [m] 5000 [m] 0 [m]
p55101[0...1] Reduction of temperature thresholds / Reduce temp_thresh
DCP_CTRL Can be changed: U, T Access level: 3
Data type: FloatingPoint32 Func. diagram: 6008, 8048
Min Max Factory setting
-20.00 [°C] 0.00 [°C] 0.00 [°C]
p55102 Heat sink temperature threshold exceeded response / Heat sink_tmp resp
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Integer16 Func. diagram: 6810
Min Max Factory setting
1 4 2
p55105 Voltage minimum / Volt min
DCP_CTRL Can be changed: U, T Access level: 3
Data type: FloatingPoint32 Func. diagram: 6810
Min Max Factory setting
0.00 [V] 600.00 [V] 30.00 [V]