Siemens sinamics dcp - p4060[0...1] TM31 analog inputs characteristic value y2; TM31 AI char y2; p4061[0...1] TM31 analog inputs wire breakage monitoring response threshold; TM31 WireBrkThresh; p4062[0...1] TM31 analog inputs wire breakage monitoring delay time; TM31 wirebrk t_del; p4063[0...1] TM31 analog inputs offset; TM31 AI offset

Siemens sinamics dcp
518 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS DCP
138 List Manual (LH21), 05/2016
Description: Sets the scaling characteristic for the analog inputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Notice: This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the response threshold for wire-breakage monitoring of the analog inputs of Terminal Module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency: For the following analog input type, the wire breakage monitoring is active:
p4056[x] = 3 (unipolar current input monitored (+4 mA ... +20 mA))
Refer to: p4056
Description: Sets the delay time for wire-breakage monitoring of the analog inputs on Terminal Module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description: Sets the offset for the analog inputs of Terminal Module 31 (TM31).
The offset is added to the input signal before the scaling characteristic.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description: Activates the absolute value generation for the analog input signals of Terminal Module 31 (TM31).
Value: 0: No absolute value generation
1: Absolute value generation switched in
p4060[0...1] TM31 analog inputs characteristic value y2 / TM31 AI char y2
TM31 Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 9566, 9568
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 100.00 [%]
p4061[0...1] TM31 analog inputs wire breakage monitoring response threshold /
TM31 WireBrkThresh
TM31 Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 9566, 9568
Min Max Factory setting
0.00 [mA] 20.00 [mA] 2.00 [mA]
p4062[0...1] TM31 analog inputs wire breakage monitoring delay time / TM31 wirebrk t_del
TM31 Can be changed: U, T Access level: 2
Data type: Unsigned16 Func. diagram: 9566, 9568
Min Max Factory setting
0 [ms] 1000 [ms] 100 [ms]
p4063[0...1] TM31 analog inputs offset / TM31 AI offset
TM31 Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 9566, 9568
Min Max Factory setting
-20.000 20.000 0.000
p4066[0...1] TM31 analog inputs activate absolute value generation / TM31 AI absVal act
TM31 Can be changed: U, T Access level: 3
Data type: Integer16 Func. diagram: 9566, 9568
Min Max Factory setting
0 1 0