2 Parameters
2.2 List of parameters
SINAMICS DCP
138 List Manual (LH21), 05/2016
Description: Sets the scaling characteristic for the analog inputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Notice: This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the response threshold for wire-breakage monitoring of the analog inputs of Terminal Module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency: For the following analog input type, the wire breakage monitoring is active:
p4056[x] = 3 (unipolar current input monitored (+4 mA ... +20 mA))
Refer to: p4056
Description: Sets the delay time for wire-breakage monitoring of the analog inputs on Terminal Module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description: Sets the offset for the analog inputs of Terminal Module 31 (TM31).
The offset is added to the input signal before the scaling characteristic.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description: Activates the absolute value generation for the analog input signals of Terminal Module 31 (TM31).
Value: 0: No absolute value generation
1: Absolute value generation switched in
p4060[0...1] TM31 analog inputs characteristic value y2 / TM31 AI char y2
TM31 Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 9566, 9568
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 100.00 [%]
p4061[0...1] TM31 analog inputs wire breakage monitoring response threshold /
TM31 WireBrkThresh
TM31 Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 9566, 9568
Min Max Factory setting
0.00 [mA] 20.00 [mA] 2.00 [mA]
p4062[0...1] TM31 analog inputs wire breakage monitoring delay time / TM31 wirebrk t_del
TM31 Can be changed: U, T Access level: 2
Data type: Unsigned16 Func. diagram: 9566, 9568
Min Max Factory setting
0 [ms] 1000 [ms] 100 [ms]
p4063[0...1] TM31 analog inputs offset / TM31 AI offset
TM31 Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 9566, 9568
Min Max Factory setting
-20.000 20.000 0.000
p4066[0...1] TM31 analog inputs activate absolute value generation / TM31 AI absVal act
TM31 Can be changed: U, T Access level: 3
Data type: Integer16 Func. diagram: 9566, 9568
Min Max Factory setting
0 1 0